Registres Contrôle Batteries - Atlantic DF ROTO VG 350 BT Notice De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.2 Registres contrôle batteries
Name
REG_HC_HEATER_TYPE
REG_HC_COOLER_TYPE
REG_HC_WCWH_STATE
REG_HC_WC_SIGNAL
REG_HC_WH_SIGNAL
REG_HC_FPS_LEVEL
REG_HC_TEMP_LVL
REG_HC_TEMP_SP
REG_HC_TEMP_LVL1
REG_HC_TEMP_LVL2
REG_HC_TEMP_LVL3
REG_HC_TEMP_LVL4
REG_HC_TEMP_LVL5
REG_HC_TEMP_IN1
REG_HC_TEMP_IN2
REG_HC_TEMP_IN3
REG_HC_TEMP_IN4
REG_HC_TEMP_IN5
REG_HC_TEMP_STATE
20
Register
R or R/W
NVM
address
201
R/W
Y
202
R/W
Y
203
R
204
R
205
R
206
Y
R/W
1
207
R/W
Y
208
R
209
R
210
R
211
R
212
R
213
R
214
R
215
R
216
R
217
R
218
R
219
R
Scaling
Access
Description/remarks
(Reg./Coil)
1
Reg
0: no heater
1: Water heater
2: Electrical heater
3: Contactor
1
Reg
0: no cooler
1: water cooler
1
Reg
State of water heater/cooler
1
Reg
Signal to cooler
1
Reg
Signal to water heater
1
Reg
Frost protection level. Allowed values: 70,
80, 90, 100, 110, 120 = 7, 8, 9, 10, 11, 12
°C.
Reg
Temperature set point level:
0: Manual summer mode.
1 to 5: correspond to temperature levels
as given by REG_HC_TEMP_LVL1 to
REG_HC_TEMP_LVL5.
1
Reg
Temperature set point.
10
Reg
Temperature level 1 * 10.
10
Reg
Temperature level 2 * 10.
10
Reg
Temperature level 3 * 10.
10
Reg
Temperature level 4 * 10.
10
Reg
Temperature level 5 * 10.
10
Reg
Temperature on sensor 1 * 10.
10
Reg
Temperature on sensor 2 * 10.
10
Reg
Temperature on sensor 3 * 10.
10
Reg
Temperature on sensor 4 * 10.
10
Reg
Temperature on sensor 5 * 10.
1
Reg + Coil
Coil 3489: State of temperature sensor on
input 1
Coil 3490: State of temperature sensor on
input 2
Coil 3491: State of temperature sensor on
input 3
Coil 3492: State of temperature sensor on
input 4
Coil 3493: State of temperature sensor on
input 5
Coil state:
0: no sensor fault
1: sensor fault

Publicité

Table des Matières
loading