Registres Contrôle Des Entrées Digitales - Atlantic DF ROTO VG 350 BT Notice De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.10 Registres contrôle des entrées digitales
Name
REG_DI_ALL
REG_DI_EXT_RUNNING_M
REG_DI_EXT_RUNNING_SPEED_LVL
REG_DI1_SF_LVL
REG_DI1_EF_LVL
REG_DI2_SF_LVL
REG_DI2_EF_LVL
REG_DI3_SF_LVL
REG_DI3_EF_LVL
Name
REG_PCU_PB_RELAYS
Register
R or R/W
NVM
address
701
R/W
702
R/W
Y
703
Y
R/W
704
R/W
Y
705
Y
R/W
706
R/W
Y
707
R/W
Y
708
R/W
Y
709
R/W
Y
Register
R or R/W
NVM
address
751
R
Access
Description/remarks
(Reg./Coil)
Reg + Coil
Digital inputs.
Coil 11201: input 1.
Coil 11202: input 2.
Coil 11203: input 3.
Coil 11204: input 4.
Coil 11205: input 5.
Coil 11206: input 6. Note: read only!
Coil 11207: input 7.
Coil value 0: input inactive.
Coil value 1: input active.
Reg
Extended running time in minutes
Reg
Fan speed level during extended running:
0: Off
1: Low speed
2: Normal speed
3: High speed
Reg
Supply fan speed level at activated digital
input 1
Reg
Extract fan speed level at activated digital
input 1
Reg
Supply fan speed level at activated digital
input 2
Reg
Extract fan speed level at activated digital
input 2
Reg
Supply fan speed level at activated digital
input 3
Reg
Extract fan speed level at activated digital
input 3
Access
Description/remarks
(Reg./Coil)
Reg + Coil
Coil Address 12001: relay for preheater on
Coil Address 12002: relay for reheater on
Coil Address 12003: common relay for
heater and preheater on