420010298800 BLU 500.1 ÷ 1200.1 PR
EN
In order to change the burner operation from natural gas to LPG you have to follow these instructions :
- Remove the blast tube. - Remove the ignition electrode. - Replace 4 Diffusers (only 700.1, 1000.1, 1200.1) with LPG version,
remove A screws. - Replace Tooth with LPG version, remove B screw. - Install the ignition electrode correctly.
- Install the blast tube .
ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH
Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas
nominal feed pressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value
of 12 mbar; for L.P.G. nom. pressure of G30/G31- 30/37 mbar, set regulator to a value
of 18 mbar).Screw up cover M
ADJUSTMENT OF THE AIR PRESSURE SWITCH
Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum
by turning regulator D to position 1.
- Start the burner and keep in low flame running, while checking that combustion is
correct. Through a small cardboard, progressively obstruct the air intake until to obtain
a CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pres-
sure port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly
increase the adjustment value of the air pressure switch until to have the burner
lockout. Remove the obstruction from the air intake, screw on the cover C and start
the burner by pressing the control box rearm button.
Note: The pressure measured at pressure port E must be within the limits of the pressure switch working range. If
not, loose the locking nut of screw F and gradually turn the same: clockwise to reduce the pressure; counterclockwi-
se to increase. At the end tighten the locking nut.
With the burner switched off, connect a DC microammeter with a 0÷50 or 0÷100 µA dial. When the burner
is running, and is properly adjusted, the value read must be steady and never be smaller than 3 µA.
CHANGE BURNER OPERATION FROM NATURAL GAS TO LPG
IONIZATION CURRENT
A
B
LGB21-LGB22 min. 3 µA
LMG21-LMG22 min. 2 µA
1
LANDIS & STAEFA
14
N
M
I
L
D
C
A
G
B
F
H
E