Electrostatic Discharge and Grounding Guide for
Cisco CPT and Cisco ONS Platforms
Cisco CPT, Cisco ONS M2, ONS M6, ONS 15454, ONS 15310-MA, ONS15310-CL, and ONS 15600
May 2011, 78-18960-03
This document uses illustrations to explain the workflow that we recommend for grounding the
Cisco CPT, Cisco ONS 15454 M2, ONS 15454 M6, ONS 15454 ANSI, ONS 15454 ETSI,
ONS 15310-MA ANSI, ONS 15310-MA ETSI, ONS 15310-CL ANSI, ONS 15600 ANSI, and
ONS 15600 ETSI chassis. It also explains best practices to be followed to prevent electrostatic discharge
(ESD) damage, which can occur when the equipment is improperly handled.
Note
The instructions in this document also applies to the Cisco ONS DWDM platform.
The following sections are included in this document:
Prerequisites, page 3
Locating and Grounding the Chassis, page 7
Installing the Line Cards, page 25
Prerequisites
Before locating and grounding any chassis, you must complete the following prerequisites:
Preparing Your Location, page 3
Preparing the Rack Room, page 5
Preparing Yourself, page 6
Preparing Your Location
This section illustrates how the building that houses the chassis must be properly grounded to the earth
ground. (See
This product requires short-circuit (overcurrent) protection to be provided as part of the building
Warning
installation. Install only in accordance with national and local wiring regulations. Statement 1045.
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Warning
Statement 1022.
78-18960-03
Figure
1.)
Electrostatic Discharge and Grounding Guide for Cisco CPT and Cisco ONS Platforms