Cisco CPT 50 Mode D'emploi page 23

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Stop. You have completed grounding the chassis.
Locating and Grounding the Cisco ONS 15600 ANSI and ONS 15600 ETSI
Bay Assembly
Before locating and grounding the Cisco ONS 15600 ANSI and Cisco ONS 15600 ETSI chassis bay
assembly, you must complete the prerequisites mentioned in
the ground point and attach a ground cable to the office ground from the Cisco ONS 15600 ANSI and
the Cisco ONS 15600 ETSI chassis bay assembly:
Note
The Cisco ONS 15600 ANSI and ONS 15600 ETSI chassis ground points are already connected to the
grounding points on the bay assembly.
Never defeat the ground conductor or operate the equipment in the absence of a suitably installed
Warning
ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are
uncertain that suitable grounding is available. Statement 213
Note
Remove any paint from the two-hole lug position on the bay front ground holes and apply the antioxidant
compound to this position.
Locate the ground access points on the bay assembly of the chassis. (See diagram 1 in
Step 1
Step 2
Connect the office ground cable to the bay front two-hole lug position. (See diagram 2 in
78-18960-03
Electrostatic Discharge and Grounding Guide for Cisco CPT and Cisco ONS Platforms
Locating and Grounding the Chassis
"Prerequisites" section on page
Figure
3. To locate
12.)
Figure
12.)
23

Publicité

Table des Matières
loading

Table des Matières