Danfoss DEVIreg Multi Guide D'installation Et Mode D'emploi page 40

Régulateur programmable sur rail-din 7 canaux
Table des Matières

Publicité

Guide d'installation et mode d'emploi DEVIreg™ Multi
I9
#3 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
I10
#3 CableOK? = NO/NC . Set up DI3 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
R75
Power calculator > Channel Power #3
I11
#3 Channel Power (max . 32000)
R8
Channel #3 > Manually On/Of
I12
#3 Manually On/Of Time – Set up period of time
for MOn or MOf status (max . 900 minutes)
I13
#3 Status On or Of for mode Heating Manually
I14
#3 Manually On/Of Start or Stop control mode .
Caution: this mode may cause overheating and
damage!
R9
Channel #3 > Channel ON/OFF
I15
#3 Channel ON/OFF If OFF – symbol # in the
line, algorithm is stopped, but real Temp . is
being shown
R11
Channel #3 > Sensor type
I17
#3 Sensor type
R12
Channel #3 > Relay Status RO/RC
I18
#3 Relay status - Set up Relay Opened (RO) or
Relay Closed (RC) for status 'Heating On'
R13
Channel #3 > Relay Test 5/30 sec .
I19
#3 Relay Test 5/30 - Every 5 sec . switching for 30 sec .
G1
Channel #4 > Regulation Type
U1
#4 Regulation Type: 1S – Single Sensor, PR –
Power Regulation
G2
Channel #4 > Temp & Hysteresis
U2
#4 Set Temperature
U3
#4 Set +-Hysteresis
G3
Channel #4 > On Time & Period
U4
#4 Set On Time
U5
#4 Set PR Period (max . 900 minutes)
G4
Channel #4 > Alarm Temps & En/Dis
U6
#4 Alarm Temp En/Dis
U7
#4 Alarm min . Temp
U8
#4 Alarm max . Temp
G5
Channel #4 > CableOK?
U9
#4 CableOK? En/Dis - Enable or Disable the
function of current monitoring in the load
U10
#4 CableOK? = NO/NC . Set up DI4 status
Normally Opened (NO) or Normally Closed (NC)
when cable is OK
G75
Power calculator > Channel Power #4
U11
#4 Channel Power (max . 32000)
40
0
1
0 – Dis
0
1
1 – NO
0
32000
0
1
900
1
0
1
0 – Of
0
1
0 – STOP
0
1
0 – OFF
0
7
1 – PT1000
0
1
0 – RC
0
1
0 – STOP
0
1
1 – 1S
-50
200
5
0 .2
6
0 .4
1
0
15
0
900
30
0
1
0 – Dis
-50
0
0
0
200
60
0
1
0 – Dis
0
1
1 – NO
0
32000
0
Enum 5
RW
3052
Enum 8
RW
3053
W
RW
3054
min .
RW
3055
Enum 11
RW
3056
Enum 6
RW
3057
Enum 7
RW
3058
Enum 9
RW
3059
Enum 10
RW
3060
Enum 6
RW
3061
Enum 1
RW
3062
°C
RW
3063
°C
RW
3064
min .
RW
3065
min .
RW
3066
Enum 5
RW
3067
°C
RW
3068
°C
RW
3069
Enum 5
RW
3070
Enum 8
RW
3071
W
RW
3072
FEC | Produced by Danfoss ©