If the PUT method is correctly requested the response is indicated with code 200 and will give back the system parameters.
If the PUT method is requested wrong the response is indicated with code 500 and will give back the system parameters.
Parameters
Value type
errors
Array

INTEGRATION

Check integration

To check the installed driver version.
POST
http://XXX.XXX.XXX.XX:3000/api/v1/integration
Where XXX.XXX.XXX.XX is the IP address of the Airzone Webserver.
The port by default is 3000.
The application where is pointed is api/v1/integration.
If the POST method is correctly requested the response is indicated with code 200 and will give back the following parameters:
{
"driver": "integrator"
}
Where "integrator" stands for the system to control with Airzone.

Modify integration

To set the integration value.
PUT
http://XXX.XXX.XXX.XX:3000/api/v1/integration
Where XXX.XXX.XXX.XX is the IP address of the Airzone Webserver.
The port by default is 3000.
speed
coldstage
Integer
heatstage
Integer
Description
request malformed
zoneid not provided
systemid not provided
zoneid out of range
Error
systemid out of range
zoneid not available
internal error
driver not provided
...
Cooling stages
Heating stages
Available values
Wrong request format
Zone not present in the request
System not present in the request
Zone not valid (0 – 32)
System not valid (0 – 32)
Zone not available
Internal error in the application
The driver is not indicated in the request
1
Low speed
2
Medium speed
3
High speed
4
Only in individual
unit zone modules
7
1
Air
2
Radiant
3
Combined
1
Air
2
Radiant
3
Combined
17
ES
EN
FR
IT
PT
DE