PUT METHOD

The PUT method is used to modify the data of a specified zone.
This method is used as below:
ES
PUT
http://XXX.XXX.XXX.XX:3000/api/v1/hvac
EN
F
With the following body
R
IT
PT
DE

PUT request parameters

The PUT method allows to modify the following parameters:
A: Flexa 3.0/Innobus Pro6, RadianT365, Acuazone, Easyzone Systems.
B: VAF, ZBS Systems.
C: Aidoo Pro.
A
B
16
Where XXX.XXX.XXX.XX is the IP address of the Airzone Webserver.
The port by default is 3000.
The application where is pointed is api/v1/hvac.
{
"systemID": n (system number),
"zoneID": m (zone number)
"parameter" (parameter to modify, e.g "setpoint"): f (value),
}
C
Parámetro
on
name
setpoint
coolsetpoint*
heatsetpoint*
mode
Tipo de
Descripción
valor
Integer
On/Off
String
Name of zone
Integer
Setpoint temperature
Setpoint temperature for cooling
Integer
mode
Setpoint temperature for heating
Integer
mode
Integer
Operation mode
Integer
Fan speed
Valores disponibles
0
Off
1
On
Name of zone
59 to 86 for ˚F
18 to 30 for ºC
59 to 86 for ºF
15 to 30 for ºC
64 to 86 for ºF
59 to 86 for ˚F
1
Stop
2
Cooling
3
Heating
4
Fan
5
Dry
7
Auto*
0
Auto