LECTRICAL WIRING WORK
All wiring must be performed by an authorized electrician.
All components procured on the site and all electric construction
should comply with the applicable local and national codes.
Be sure to use a dedicated power circuit.
Do not share a common source with other equipment.
Fix cables so that cables do not make contact with the pipes
(especially on high pressure side).
Make sure to connect power supply cables in normal phase. If
connected in reverse phase, the remote controller of indoor unit
indicates "U1" and the equipment cannot operate. Change any
two of the three power supply cables (L1, L2, L3) to correct
phase.
If the contact in the magnetic switch should be forcibly turned on
while the equipment is inoperative, the compressor will burn out.
Never try to forcibly turn on the contact.
Never squeeze bundled cables into a unit.
When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the installation hole.
(Refer to
figure
11)
A
Inside
B
Outside
1
Wire
2
Bush
3
Nut
4
Frame
5
Hose
Follow the electric wiring diagram for electrical wiring works.
Grounding
resistance
regulations.
Wiring of power supply and the units
Refer to the installation manual attached to the indoor unit for wiring
of indoor units, etc.
Attach an earth leak detector and fuse to the power supply line.
figure
10).
I
Pair
II
Twin
III
Triple
IV
Double Twin
M
Master
S
Slave
1
Earth leak detector
2
Fuse
3
Remote controller
Power supply
Field
Model
fuse
Wire type
R(Y)P200
25 A
H05VV-U5G
R(Y)P250
32 A
H05VV-U5G
(1) Only in protected pipes, use H07RN-F when protected pipes are not used.
Installation manual
6
should
be
according
to
Wire type of
wiring between
(1)
Size
the units
Wiring size must
H05VV-U4G2.5
comply with the
applicable local and
H05VV-U4G2.5
national code
Point for attention regarding quality of the public electric power
supply
This equipment complies with EN/IEC 61000-3-11
the system impedance Z
interface point between the user's supply and the public system. It is
the responsibility of the installer or user of the equipment to ensure,
by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a system
impedance Z
sys
R(Y)P200
R(Y)P250
Equipment complying with EN/IEC 61000-3-12
T
EST OPERATION
For the test run procedure, refer to the indoor unit installation manual.
D
ISPOSAL REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
W
IRING DIAGRAM
: FIELD WIRING
national
L
: LIVE
N
: NEUTRAL
: TERMINAL
: CONNECTOR
: WIRE CLAMP
: PROTECTIVE EARTH (SCREW)
(See
BLK
: BLACK
BLU
: BLUE
ORG
: ORANGE
RED
: RED
WHT
: WHITE
YLW
: YELLOW
: DO NOT OPERATE THE UNIT BY SHORTCIRCUITING S1LP
: USE COPPER CONDUCTORS ONLY
L1........................... RED
L2........................... WHITE
L3........................... BLACK
N ............................ BLUE
A1P,A2P................. PRINTED CIRCUIT BOARD
BS1........................ PUSH BUTTON (FORCED DEFROST - PUMP
C1R,C2R ............... CAPACITOR (M1F-M2F)
DS1........................ SELECTOR SWITCH (DEFROST)
F1C........................ OVER-CURRENT RELAY
F1U,F2U ................ FUSE (250 V, 10 A)
F3U........................ FIELD FUSE
(1) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current ≤75 A.
(2) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and ≤75 A per phase.
is less than or equal to Z
sys
less than or equal to Z
.
max
Z
(Ω)
max
0.25
0.24
DOWN)
(1)
provided that
at the
max
(2)
R(Y)P200+250B8W1
Split System air conditioners