Testing; Test Outputs; Test Rs-485 Credential Reader; Test Input Leds - Schlage ENGAGE CTE Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Test Outputs

Regardless of the CTE mode, the Test buttons for the LOCK, ALARM
and AUX outputs can always be used. Even when commissioned and
LINKED, CTE Test buttons will change the state of the outputs when
held in.
LOCK
When pushed the LOCK output
Test Button
relay, LOCK power output, and
the CTE amber LOCK LED will
change state.
ALARM
When pushed the ALARM
Test Button
output relay, ALARM power
output, and the CTE amber
AUX LED will change state.
AUX
When pushed the AUX output
Test Button
relay, AUX power output, and
the CTE amber AUX LED will
change state.

Test RS-485 Credential Reader

Use this button push sequence to test the reader connection in any
CTE MODE.
1. Test and sync the CTE with the RS-485 reader.
2. Push and release the CTE SCHLAGE button, followed by two
quick pushes on the FDR button.
3. A correctly wired MTB11, MTB15, MT11-485 or MT15-485 will
beep and blink amber three times.

Test Input LEDs

In any mode the inputs to the CTE can tested by checking the input
LEDs.
REN
Short the REN & GND input, the
amber REN LED will light. The
SETTINGS switch above the
inputs will reverse this logic.
REX
Short the REX & GND input, the
amber REX LED will light. The
SETTINGS switch above the
inputs will reverse this logic.
DPS
Short the DPS & GND input, the
amber DPS LED will light. The
SETTINGS switch above the
inputs will reverse this logic.
Test CTE Wi-Fi connection when enabled and used after
commissioning
The Wi-Fi is first set during CTE commissioning, or after
commissioning when connected with the ENGAGE mobile app.
1. Use the ENGAGE mobile app to get audits from CTE.
2. The app will display audit data and Wi-fi results.
Audit Result
Meaning
TLS Certificate
The certificate expired and will
Validation Failed
automatically renew.
Associated with
Connection to the wireless router was
network AP
successful.
Connected to host
Internet connection to the server was
successful.
8

Testing

Check the lock/
unlock of the wired
strike, trim or QEL.
Alarm will sound
when wired
correctly.
If wired correctly
will signal the Auto
Operator.
When REN is wired to
an external switch to
signal request to enter.
When REX is wired to
the inside lever or push
pad switch, an inside
lever turn or push pad
active will be indicated
with the REX LED.
When wired to a door
DPS, an open door will
be indicated with the
amber DPS LED.

Test LINKED status

Tests the CTE LINKED status only after the CTE is commissioned and
LINKED.
1. Connect to the Gateway with the ENGAGE mobile app.
2. Check the Gateway's "Managed LINKED Devices" to confirm that
the CTE is LINKED. The app will show all devices linked to the
Gateway and their signal strengths.

Status LED Indications

Location of Status LED

Status LED Indications Table

Solid Red
Solid Green
3x Green Flash on power up
3x Red Flash on power up
1x Long Green Flash
2x Red Flash
5x Green Flash
Steady Blue Flash
Steady Amber Flash
Alternating Red/Green Flash

Quick Reference Guide

Bluetooth
Press and release SCHLAGE button when
advertising
FDR status LED is illuminated. This will allow
a 2 minute time for the ENGAGE Mobile app
to connect.
Factory Default
Press and hold FDR button for 5 seconds,
Reset
then press SCHLAGE button 3 times.
FACTORY DEFAULT mode LED will illuminate.
Enter Construction
Press and hold SCHLAGE button for
Mode
5 seconds. FACTORY DEFAULT and
CONSTRUCTION mode LEDs will both
illuminate. Present credential to the reader
within 20 seconds to create the Master
Construction Credential. Once created, the
FACTORY DEFAULT Mode LED will turn off,
and the CONSTRUCTION Mode LED will
remain illuminated.
Test Outputs
Press the LOCK, ALARM, or AUX buttons to
test the LOCK, ALARM, or AUX outputs. Each
button will activate both the Dry and Powered
contacts.
IP LINKING
Use the IP Gateway to LINK with a
commissioned CTE. After commissioning no
action is need at the CTE to link.
Temporary
Press and hold the Schlage button for 5
de-linking from
seconds to temporarily de-link from Gateway.
Gateway
LOCK Relay in secure state
LOCK Relay in passage state
Power On Self Test (POST) passed
Power On Self Test (POST) failed
Factory default reset successful
Factory default reset failed
Master construction credential
programmed
Bluetooth active
Wi-Fi active
Firmware update in progress

Publicité

Table des Matières
loading

Produits Connexes pour Schlage ENGAGE CTE

Table des Matières