Credential Readers; Reader Connections Table; Power Failure Modes; Construction Mode - Schlage ENGAGE CTE Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Credential Readers

MTB11, MTB15, MT11-485 and MT15-485 readers are UL294 listed for
use with the CTE.

Reader Connections Table

READER - RS485
POWER 12V
Reader power (red
wire)
POWER GND
Reader power
ground (black)
DATA A
RS485 data A
(pink)
DATA B
RS485 data B
(tan)
Reader Connections: RS-485 and Power Ground. Located in the
READER box under the FDR and SCHLAGE buttons.
Connect the shield of the reader cable to the CTE (GND). Do not
L
connect the cable shield at the credential reader.

Power Failure Modes

The CTE lock relay can be configured to fail safe (fail unlocked) or fail
secure (fail locked) by wiring the door hardware to either NO or NC,
and selecting a failsafe or fail secure locking device.
UL listed electronic locking devices may need a UL listed access
control or burglar power supply with battery backup for the CTE to
control their power failure mode (example: Schlage models PS902,
PS904, PS906).
Programming may be performed by commissioning the CTE in an
ENGAGE account.
Description
12 VDC power to RS485
reader
Electrical ground
(common) for the CTE
Data A communication for
RS485 reader
Data B communication for
RS485 reader

Construction Mode

Construction mode is used to allow access before the CTE controller is
commissioned, and for testing purposes.
Enabled by default.
The CTE controller will remain in construction access mode until
the mode is cancelled with an FDR as described below.
No audits are captured while the CTE controller is in construction
access mode.

CTE controller with connected reader

1. Remove the CTE lid.
2. Press and hold the Schlage button for five seconds, note the CTE
MODE indicator switches on for Construction mode.
3. Present a credential to the reader within 20 seconds of releasing
the Schlage button.
4. The CTE STATUS LED and the reader's LED will blink green five
(5) times.
5. This credential becomes the master construction credential.
If the credential is not presented within 20 seconds, a
L
timeout will occur. Repeat steps 2-5 above.

Program construction access mode user credentials

The master construction credential must be programmed
L
before programming construction access mode with user
credentials.
1. Present the master construction credential to the reader.
2. The STATUS LED and the reader's LED will light green for 20
seconds.
3. Present the USER credential to be programmed within 20
seconds.
4. The STATUS LED and the reader's LED will blink green five (5)
times.

Cancel construction access mode

Perform a factory default reset (FDR). See the next section for
instructions.
When construction mode is cancelled, the master construction
credential and all other USER credentials added using the master
construction credential will no longer function.
TIPS
L
Use the same master construction credential for all the controllers
in the facility.
If you present the first card with a new controller to create the
master construction credential and the card is not accepted, the
controller has either been programmed or already has a master
construction credential.
If the master construction credential cannot be located, or to put
the controller back into construction access mode, perform a FDR.
See next section for more information.

Factory Default Reset (FDR)

All information in the CTE will be deleted and
reset to factory defaults!
1. Remove the CTE lid.
2. Press and hold the FDR button then release after 5 seconds.
3. Then press the Schlage button three (3) times.
4. After a successful FDR, the CTE STATUS LED and the reader's
LED will blink green for one second, and the reader will beep for
one second.
5. The MODE LED will now indicate Factory Default mode.
6. Replace the lid.
NOTICE
7