Applicable Controls - Toshiba Carrier MMC-AP0188HPUL Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Wiring between indoor and outdoor units
NOTE
series, refer to the Installation Manual attached to the outdoor unit to be connected.
Wiring example
Outdoor Power supply
Circuit breaker
Outdoor unit
Header outdoor
Earth
terminal
S: The ground of a
shielded wire
Control wiring between indoor and outdoor units (Shield wire)
Control wiring between indoor units (Shield wire)
Indoor unit
Indoor unit
Earth
Earth
Indoor power supply
208/230V-1-60 Hz
Remote controller
Circuit breaker,
Pull box
Pull box
Power switch
Address setup
Set up the addresses as per the Installation Manual supplied with the outdoor unit.
35-EN
1115652706_01_EN.indd 18
1115652706_01_EN.indd 18
Outdoor Power supply
Circuit breaker
Outdoor unit
Follower outdoor
Earth
terminal
S: The ground of a shielded wire
Control wiring between outdoor units (Shield wire)
Indoor unit
Indoor unit
Earth
Earth
Remote controller
Remote controller
Pull box
Group control
8

Applicable controls

REQUIREMENT
When the air conditioner is used for the fi rst time, it will
take some moments after the power has been turned
on before the remote controller becomes available
for operations: This is normal and is not indicative of
trouble.
Concerning the automatic addresses (The automatic
addresses are set up by performing operations on
the outdoor interface circuit board.)
While the automatic addresses are being set up,
no remote controller operations can be performed.
Setup takes up to 10 minutes (usually about
5 minutes).
When the power is turned on after automatic address
setup.
It takes up to 10 minutes (usually about 3 minutes)
for the outdoor unit to start operating after the power
has been turned on.
Before the air conditioner was shipped from the
factory, all units are set to [STANDARD] (factory
default). If necessary, change the indoor unit settings.
The settings are changed by operating the wired
remote controller.
* The settings cannot be changed using only a wireless
remote controller, simple remote controller or group
control remote controller by itself so install a wired
remote controller separately as well.
– 18 –
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table:
Do NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with the
product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT31E). (There are more CODE No.)
1
3
4
6
1
5
2
1
Push and hold button
and "TEMP."
button simultaneously for at least 4 seconds.
After a while, the display fl ashes as shown in
the fi gure. Confi rm that the CODE No. is [01].
If the CODE No. is not [01], push
button
to clear the display content, and repeat the
procedure from the beginning. (No operation
of the remote controller is accepted for a while
after
button is pushed.)
(While air conditioners are operated under the
group control, "ALL" is displayed fi rst. When
is pushed, the indoor unit number
displayed following "ALL" is the header unit.)
(* Display content varies with the indoor
unit model.)
10/8/20 8:11 PM
10/8/20 8:11 PM
EN
FR
ES
36-EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mmc-ap0248hpulMmc-ap0308hpulMmc-ap0368hpulMmc-ap0488hpul

Table des Matières