Wire connection

REQUIREMENT
Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
Pass the wires through the bushing of wire connection holes of the indoor unit.
Keep a margin (Approx. 3.9" (100 mm)) on a wire to hang down the electrical control box at servicing.
The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
1
Loosen the cover mounting screws (2 positions) of the electrical control box, and then remove the
cover.
2
Connect the indoor power supply wire, system interconnection wires and the remote controller wire to
the terminal block of the electrical control box.
3
Tighten screws of the terminal block securely, and fi x the wires with code clamp attached to the
electrical control box. (Do not apply tension to the connecting section of the terminal block.)
4
Mount the cover of the electrical control box so that it does not pinch the wires.
Electrical control
Two screws
box cover
Connecting power supply wire and the system interconnection wire
Power supply
Interconnection wire / Remote
terminal block
controller terminal block
(Uv (U1)) (Uv (U2)) (A) (B)
Power supply wire
R
S
0.3"
(L)
(N)
0.3"
(10 mm)
(10 mm)
2"
1.1"
(50 mm)
(30 mm)
Earth wire
Power supply wire
33-EN
1115652706_01_EN.indd 17
1115652706_01_EN.indd 17
– 17 –
P.C. board
Terminal block
System interconnection
wires
Run the system
interconnection wire here
through the clamp base and
fi x it with a cord clamp.
Power supply wire
Run the power supply
wire here through the
clamp base and fi x it
with a cord clamp.
See the fi gure on the left
for connecting wires to the
terminal block.
Power supply wire
Remote controller wiring
Strip off approx. 0.3" (9 mm) the wire to be connected.

Wiring diagram

Terminal block for
remote controller
Terminal block
wiring of indoor unit
Remote
A
A
controller
B
B
unit
Remote controller wire (Locally procured)
Remote controller wire
Run the remote
Remote controller
controller wire through
wire
the cord clamp.