5. CONTROL PANEL

5.1 THE CONTROL PANEL

a
4001844
Speed
c
Golden Valley, MN 55422
Country of origin: China
Fig. 8. Resideo AquaPUMP control panel
Position
A
Display showing the actual pump power
consumption in Watts and reference flow in
USgpm. Display alternates between Watt and
GPM every 5 seconds.
B
Pump setting LEDs
C
Mode select button for changing pump setting
NOTE:
GPM value and flow indicator are uncalibrated.

5.2 FIRST POWER-UP

The display is on and in Auto mode (position 0 in Fig. 9) the
first time the panel is powered on.
NOTE:
Display shows "E#" when the pump is not operating
properly (see section 10). (E1, E2, E3 or ER)
5.3 DISPLAY
The Resideo AquaPUMP variable speed circulator has nine
pump settings which can be selected with the Mode button.
Every time the Mode button is pressed (see Fig. 8, C) the
pump setting is changed to the next mode.
A full cycle through the available modes requires nine button
presses.
The selected pump setting is indicated by one of nine
different light fields (see Fig. 9).
Pressure Curve
Input
b
Auto
Description
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
speed
7
6
5
Fig. 9. Pump setting LEDs
See section 9, Pump settings and pump performance, for
information about the function of each setting.
Position
0
AUTO (factory setting)
1
PC1 Lowest proportional-pressure curve
2
PC2 Highest proportional-pressure curve
3
PC3 Lowest constant-pressure curve
4
PC4 Highest constant-pressure curve
5
Constant speed curve, speed I
6
Constant speed curve, speed II
7
Constant speed curve, speed III
8
Analog input

6. SETTING THE PUMP

6.1 PUMP SETTING FOR SYSTEM TYPE
NOTE:
Optimum energy savings & comfort can be achieved
by careful selection of the correct operation mode
(see Fig. 10).
Recommended and alternative pump settings are shown
below:
Image
System Type
A
Under floor
heating
(Radiant
single zone)
B
Two-pipe
(parallel)
systems
C
One-pipe
(series)
systems
*See pump settings and pump performance (section 9)
5
3
4
pressure curve
aut o
Description
Recommend
ed Setting
Alternative Setting
Auto
Highest constant-
pressure curve (pc4)*
or Lowest constant-
pressure curve (pc3)*
Auto
Highest proportional
pressure (pc2)*
Lowest
Highest proportional
proportional
pressure (pc2)*
pressure
curve (pc1)*
8
input
2
1
0
33-00543EF—01