AQUAPUMP™ 3-SPEED CIRCULATION PUMPS
Fig. 8. Circulator pump wiring.

PUMP OPERATION

WARNING
Pump Damage.
Do not start the pump until it has been filled with
water and the system has been purged of air.

7. Starting the pump

• Do not start the pump until it has been filled with water
and the system has been purged of air.
• Open the service valves on both sides of the pump to fill
the system with water. Check for leaks.
• Turn the air vent screw in the middle of the housing
counterclockwise until you hear air escape from the
system. Placing a rag under the vent holes will help collect
water.
62-0383EFS—11
• Run the pump with the air vent open. Water will drip from
the air vent holes. Then, when all air is vented, close the air
N (NEUTRAL)
vent screw by screwing it clockwise back into place.
L (LINE, HOT)
GROUND
WARNING
Risk of scalding/burning
Depending on water temperature and pressure of the
system, hot vapor or liquid can escape if the air vent
screw is completely loosened.
Depending on water temperature and how long the
pump has been running, the pump can become very
hot.
M32875

8. Speed selection

• Turn the speed adjustment knob clockwise to increase the
speed (see Fig. 9).
• See Figs. 2-4 on page 2 for the flow curves of each pump
at the three different speeds.
• Select a speed to obtain proper flow needed for correct
system operation.
4
SPEED
ADJUSTMENT
KNOB
SERVICE
VALVES
AIR VENT
SCREW
Fig. 9. Bleed the circulator by loosening
the air vent screw.
M32876