Technical Data; Inlet Pressure - resideo AquaPUMP PCVF-ECM2020/U Instructions D'installation

Pompes de circulation à vitesse variable
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
TECHNICAL DATA AND
INSTALLATION DIMENSIONS

11.1 TECHNICAL DATA

Supply voltage: 1x 115 V ± 10% 60 Hz
Minimum
Amp
0.05
Watt
5
Analog input: DC voltage only
Min. Voltage
Single Type
Limit
2-10V
0 VDC
Motor protection: The pump requires no external motor pro-
tection.
Maximum fluid temperature: 230°F (110°C) maximum
Maximum working pressure: 150 psi (10 bar).
Maximum relative air humidity (rh): 95%
Enclosure class: Type 2
Insulation class: H
Certification: ETL listed for US and Canada (conforms to UL
STD 778 certified to CSA STD C22.2 NO.108-01)
NSF 372 (stainless steel models)

INLET PRESSURE

Minimum inlet pressure in relation to liquid temperature:
Sound pressure level: The sound pressure level of the pump
is lower than 43 dB(A).
Ambient temperature: 0°C (32°F) - 40°C (104°F)
Pumped liquids: Water or water glycol mix.
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
33-00543EF—01 M.S. 12-20 | Printed in United States
www.resideo.com
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Tous droits réservés. Ce produit est fabriqué par Resideo Technologies, Inc. et ses sociétés affiliées.
Maximum
0.72
45
Max. Voltage
Max. Current
Limit
Limit
10 VDC
32 mA
Liquid Temperature
150°F (65°C)
3.0 ft (0.91 m)
167°F (75°C)
4.4 ft (1.34 m)
194°F (90°C)
9.2 ft (2.8 m)
230°F (110°C)
36.1 ft (11.0 m)
WARNING
This pump is not rated to pump flammable liquids
such as diesel oil, gasoline or similar liquids
Liquid temperature: 2°C (36°F) - 110°C (230°F)
To avoid condensation in the control box and stator, the liquid
temperature must always be higher than the ambient
temperature.
Liquid Temperature
Ambient
Temperature
Min.
0°C (32°F)
2°C (35.6°F)
10°C (50°F)
10°C (50°F)
20°C (68°F)
20°C (68°F)
30°C (86°F)
30°C (86°F)
35°C (95°F)
35°C (95°F)
40°C (104°F)
40°C (104°F)
CAUTION
Since water conditions can vary with geographical
location (i.e. amount and type of dissolved solids) it
is recommended that the operating temperature of
the liquid for open (potable) systems be kept as low
as possible (i.e. below 150°F or 65°C) to avoid
crystalization of calcium.
VOLUTE MATERIAL
Cast iron: For closed systems (boiler loops)
Stainless steel: Open or closed systems (potable hot water or
boiler loops)
Certified <0.25 weighted average percent lead (NSF 372) and
complies with California Health and Safety code section
116875 (commonly known as AB1953).
Minimum Inlet Pressure
Max.
110°C (230°F)
110°C (230°F)
110°C (230°F)
110°C (230°F)
90°C (194°F)
70°C (158°F)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Aquapump pcvf-ecm2020-lf/u

Table des Matières