POSITION OF POTENTIOMETERS AND JUMPERS

Remove the lid of the body by unscrewing the 4 screws. Caution : do not loosen or damage the cable
connections, and adjust the potentiometer.
OBSERVE PRECAUTIONS
E S D

PNEUMATIC CONNECTION

The pneumatic ports are as follows : 1 = supply pressure, 2 = pressure output, 3 = exhaust
Each screw connection is lined with a fitting synthetic sealing disc. PTFE (polytetrafluoroethylene) sealing tape
and hemp should not be used as they may get into the inside of the valve and damage it. Use an appropriate
silencer at port (3). The exhaust time can be longer according to the type of silencer you use.
The diameter of the pneumatic lines must be adjusted to the nominal diameter of the valve. the diameter of
output line (2) must be larger or equal to that of input line (1).
The supply pressure must always be less than the MAP value (max. allowable pressure).
control of the pressure sensor
5M-1002
24
All manuals and user guides at all-guides.com
SENTRONIC G 1/8, G 1/4, G 1/2, G 1
P1
= Span adjustment
P2
= Offset adjustment
P4-P5 = Calibration of pressure sensor : DO NOT MODIFY THIS ADJUSTMENT
P6
= Pressure switch adjustment (window size)(1,4 . . . 6%)
P7
= Proportional gain (1. . .11)
WARNING
FOR HANDLING
ELECTROSTATIC
DISCHARGE
SENSITIVE DEVICES
Sentronic with internal
2
P
U
3
1
This product contains electronic components sensitive to
electrostatic discharge. If a person or an object come in contact
with the electrical components of the product, there will be an
electrostatic charge which can damage or destroy the product.
To reduce the risk of electrostatic discharge, please observe the
handling precautions and recommendations contained in standard
EN100 015-1 at all times. Do not connect or disconnect this device
when it is energised.
control of the pressure sensor
Coil
P2
P1
Sentronic with external
4
2
P
U
3
1
P5
P4
P7
P6
max.