Checkout - Honeywell F300E Guide D'installation

Electronic air cleaner
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8. Wire the power cord ground lead to the ground choke assembly using wire nut. Secure ground connection to
the green ground screw on the wiring compartment barrier.
9. Replace power supply cover and access door.
REMOVING COVER
FROM POWER BOX.
1

Checkout

Visually check the installation and make sure that:
Airflow is in the direction of the arrow on the electronic cells.
Metal mesh prefilter is on the upstream side and media postfilter (if used) is on the downstream side.
Cell handles face outwards.
Electronic cell and prefilter are clean and dry.
Turning vanes and transitions, if used, are properly installed.
Joints in sheetmetal between electronic air filter and heating and cooling system are sealed.
All sheetmetal connections are complete.
Original furnace filter has been removed and blower compartment is cleaned.
When you have verified that checkout has been completed:
Replace any access doors removed during the Installation or Checkout.
Run the furnace or cooling system through one complete cycle to make sure the system operates as desired.
F300 Electronic Air Cleaner 68-0240EF—08
2
3
M20806
WIRING
COMPARTEMENT
ELECTRONIC
AIR CLEANER
BLACK
BROWN
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
THE AIR CLEANER CAN BE COMPLETELY ISOLATED FROM
THE ELECTRICAL CIRCUIT OF THE HVAC SYSTEM UNLESS
REQUIRED BY LOCAL CODE TO USE SAME CIRCUIT. ANY
CONVENIENT HOUSE CIRCUIT CAN POWER AIR CLEANER,
REGARDLESS OF ELECTRICAL RATING OF HVAC SYSTEM.
GROUND
CHOKE
2
L1 (HOT)
1
L2
M32905
13

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

F300aF300b

Table des Matières