Watlow RMA EZ-ZONE RM Guide De L'utilisateur page 69

Table des Matières

Publicité

Valeurs par défaut d'ensemble CIP implicite RMC
Assembly
Assembly
Class, Instance,
Members
Attritbute
1
0x77, 0x01, 0x01
2
0x77, 0x01, 0x02
3
0x77, 0x01, 0x03
4
0x77, 0x01, 0x04
5
0x77, 0x01, 0x05
6
0x77, 0x01, 0x06
7
0x77, 0x01, 0x07
8
0x77, 0x01, 0x08
9
0x77, 0x01, 0x09
10
0x77, 0x01, 0x0A
11
0x77, 0x01, 0x0B
12
0x77, 0x01, 0x0C
13
0x77, 0x01, 0x0D
14
0x77, 0x01, 0x0E
15
0x77, 0x01, 0x0F
16
0x77, 0x01, 0x10
17
0x77, 0x01, 0x11
18
0x77, 0x01, 0x12
19
0x77, 0x01, 0x13
20
0x77, 0x01, 0x14
Assembly
Assembly
Class, Instance,
Members
Attritbute
1
Cannot be changed
2
0x77, 0x02, 0x01
3
0x77, 0x02, 0x02
4
0x77, 0x02, 0x03
5
0x77, 0x02, 0x04
6
0x77, 0x02, 0x05
7
0x77, 0x02, 0x06
8
0x77, 0x02, 0x07
9
0x77, 0x02, 0x08
10
0x77, 0x02, 0x09
11
0x77, 0x02, 0x0A
12
0x77, 0x02, 0x0B
13
0x77, 0x02, 0x0C
14
0x77, 0x02, 0x0D
15
0x77, 0x02, 0x0E
16
0x77, 0x02, 0x0F
17
0x77, 0x02, 0x10
18
0x77, 0x02, 0x11
19
0x77, 0x02, 0x12
20
0x77, 0x02, 0x13
21
0x77, 0x02, 0x14
Module RMA Watl ow EZ- Z ONE
CIP Implicit Assembly
Originator (Master) to Target (RMC)
RM Module
Data Type
DINT
Control Loop 1, Closed Loop Set Point
DINT
Control Loop 2, Closed Loop Set Point
DINT
Control Loop 3, Closed Loop Set Point
DINT
Control Loop 4, Closed Loop Set Point
DINT
Control Loop 1, Open Loop Set Point
DINT
Control Loop 2, Open Loop Set Point
DINT
Control Loop 3, Open Loop Set Point
DINT
Control Loop 4, Open Loop Set Point
DINT
Control Loop 1, User Control Mode
DINT
Control Loop 2, User Control Mode
DINT
Control Loop 3, User Control Mode
DINT
Control Loop 4, User Control Mode
DINT
Alarm 1, Alarm High Set Point
DINT
Alarm 2, Alarm High Set Point
DINT
Alarm 3, Alarm High Set Point
DINT
Alarm 4, Alarm High Set Point
DINT
Alarm 1, Alarm Low Set Point
DINT
Alarm 2, Alarm Low Set Point
DINT
Alarm 3, Alarm Low Set Point
DINT
Alarm 4, Alarm Low Set Point
CIP Implicit Assembly
Target (RMC) to Originator (Master)
RM Module
Data Type
Binary
DINT
Analog Input 1, Analog Input Value (filtered)
DINT
Analog Input 1, Input Error
DINT
Analog Input 2, Analog Input Value (filtered)
DINT
Analog Input 2, Input Error
DINT
Analog Input 3, Analog Input Value (filtered)
DINT
Analog Input 3, Input Error
DINT
Analog Input 4, Analog Input Value (filtered)
DINT
Analog Input 4, Input Error
DINT
Alarm 1, Alarm State
DINT
Alarm 2, Alarm State
DINT
Alarm 3, Alarm State
DINT
Alarm 4, Alarm State
DINT
Alarm 5, Alarm State
DINT
Alarm 6, Alarm State
DINT
Alarm 7, Alarm State
DINT
Alarm 8, Alarm State
DINT
Control Loop 1, Output Power
DINT
Control Loop 2, Output Power
DINT
Control Loop 3, Output Power
DINT
Control Loop 4, Output Power
®
Parameter
Parameter
Device Status
6 6
Parameter
PLC
Class, Instance,
Data Type
Attritbute
0x6B, 0x01, 0x01
REAL
0x6B, 0x02, 0x01
REAL
0x6B, 0x03, 0x01
REAL
0x6B, 0x04, 0x01
REAL
0x6B, 0x01, 0x02
REAL
0x6B, 0x02, 0x02
REAL
0x6B, 0x03, 0x02
REAL
0x6B, 0x04, 0x02
REAL
0x97, 0x01, 0x02
DINT
0x97, 0x02, 0x02
DINT
0x97, 0x03, 0x02
DINT
0x97, 0x04, 0x02
DINT
0x6D, 0x01, 0x01
REAL
0x6D, 0x02, 0x01
REAL
0x6D, 0x03, 0x01
REAL
0x6D, 0x04, 0x01
REAL
0x6D, 0x05, 0x01
REAL
0x6D, 0x06, 0x01
REAL
0x6D, 0x07, 0x01
REAL
0x6D, 0x08, 0x01
REAL
Parameter
PLC
Class, Instance,
Data Type
Attritbute
none
DINT
0x68, 0x01, 0x01
REAL
0x68, 0x01, 0x02
DINT
0x68, 0x02, 0x01
REAL
0x68, 0x02, 0x02
DINT
0x68, 0x03, 0x01
REAL
0x68, 0x03, 0x02
DINT
0x68, 0x04, 0x01
REAL
0x68, 0x04, 0x02
DINT
0x6D, 0x01, 0x09
DINT
0x6D, 0x02, 0x09
DINT
0x6D, 0x03, 0x09
DINT
0x6D, 0x04, 0x09
DINT
0x6D, 0x05, 0x09
DINT
0x6D, 0x06, 0x09
DINT
0x6D, 0x07, 0x09
DINT
0x6D, 0x08, 0x09
DINT
0x97, 0x01, 0x0F
REAL
0x97, 0x02, 0x0F
REAL
0x97, 0x03, 0x0F
REAL
0x97, 0x04, 0x0F
REAL
C h ap itr e  8 An ne x e

Publicité

Table des Matières
loading

Table des Matières