Save parameters 0: No
0..10 VDC holdback 0 – 120
0..10 VDC Disable / Enable 0: OFF
Current fan speed (%) 0 – 100 %
Current fixed fan speed 0 – 4
Temperature Setpoint 150 – 350 °C (/10)
Current Temperature - 500 – 1000 (/10)
Pressure Setpoint 0 – 999 Pa
Current pressure 0 – 999 Pa
CO
Current CO
Alarm 1 address 0/1
Alarm 2 address 0/1
Alarm 3 address 0/1
Alarm 4 address 0/1
Alarm 5 address 0/1
Alarm 6 address 0/1
Alarm 7 address 0/1
Alarm 8 address 0/1
Alarm 9 address 0/1
Alarm 10 address 0/1
To save configuration parameters, write 22 to the register 49, then settings are saved to EEPROM mem-
ory, controller reloads.
Alarms
ECO automation alarms
Indication
Meaning (see device technical manual for alarm description)
Activated heat exchanger antifreeze protection
A.01
External protection activated for example, fire emergency exit, filter contamination (pressure
A.02
rely activated), fans
Return water critical temperature
A.03
"P-mA" of water heater
A.04
Low unit's power voltage
A.05
Extracted air temperature sensor fault
A.06
Supply air temperature sensor fault
A.07
Return water temperature sensor fault of water heater
A.08
Ambient air temperature sensor fault
A.09
54
All manuals and user guides at all-guides.com
22: Yes
1: ON
Setpoint 0 – 999 ppm
2
0 – 999 ppm
2
Holding
0x36
register
Holding
0x37
register
Holding
0x38
register
Input register
0x01
Input register
0x02
Input register
0x03
Input register
0x04
Input register
0x05
Input register
0x06
Input register
0x07
Input register
0x08
Coil
0x01
Coil
0x02
Coil
0x03
Coil
0x04
Coil
0x05
Coil
0x06
Coil
0x07
Coil
0x08
Coil
0x09
Coil
0x0A
www.salda.lt
49
50
51
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10