Installing The Stove; Stove Rotating; Minimum Distance From Combustible Or Load-Bearing Walls - Konigshutte Virgo 28/865 Instructions

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Installing the stove

The floor on which the stove is installed must be even
and horizontal. The stove may only be installed on an
adequate load-bearing floor. The stove can be stood
on a metal floor sheet or glass sheet to protect the
flooring.
If the flooring or carpet is inflammable, a stable and
non-combustible spark protection plate must be used.
This must extend 50 cm to the front and 30 cm to each
side beyond the edge of the combustion chamber
opening. Under the stove no spark protection plate is
required.

Stove rotating

The stove is delivered with the arrest engaged
(non-rotating). If the stove should rotate, the arrest on
the underside of the footrest must be unscrewed and
removed (see Fig.2).
Attention: Only with the top connection can the stove
be rotated via the footrest in 5 stages, 45°
to the left and the right.
Fig.1 Footrest
Fig.2 Arrest
12
Minimum distance
from combustible or load-bearing walls
There must be no objects made of combustible materi-
als within a distance of 100 cm of the stove's radiation
area, measured from the combustion chamber's in-
spection glass, nor may any be placed within this area
subsequently.
Depending on whether the stove is installed with the
arrest engaged (non-rotating) or rotating, different min-
imum wall distances that must be complied with apply,
based on the position of the combustion chamber door
to the set-up wall or side wall (see Fig. 3 to 6).
Stove with arrest engaged
The wall distances for non-rotating installation are pre-
sented below.
40 cm
Fig.3 Stove with arrest engaged,
installed straight in corner
25 cm
Fig.4 Stove with arrest engaged,
installed diagonally in corner
40 cm

Publicité

Table des Matières
loading

Table des Matières