Technical Data; Regulations To Be Observed; Chimney Design; Combustion Air Supply - Konigshutte Virgo 28/865 Instructions

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Technical Data

● Nominal thermal output ................................. 5,5 kW
● Room heat output .......................................... 5,5 kW
● Height to middle of the connector pipe
with the connection at the back
● Height to the top edge of connector pipe
with the connection at the top .....................1128 mm
● Connection pipe ...................................... Ø 150 mm
● max. Weight................................................... 155 kg
● Height to middle
of combustion air connection ....................... 180 mm
● Connection combustion air ...................... Ø 125 mm
● Operating mode ........................ Intermitting burning
If the rear connection is used, the appliance can no
1)
longer rotate.

Regulations to be observed

● Local and building law regulations
● The stove must be installed by a professional and
connected to the chimney. The specific national reg-
ulations for safe installation of the connector must be
complied with. The connecting piece used must pos-
sess an opening for cleaning.
● The stove must be regularly checked by a
professional.
The heating stove's fire door is self-closing; it is there-
fore approved for connection to chimneys with multiple
connections.

Chimney design

The chimney design is according to DIN EN 13384-1
and -2 or to the specific national regulations. The chim-
ney must comply with the temperature class T400.
Necessary data
Closed operation
with billet wood / lignite briquettes:
● Nominal thermal output ......................... 5,5 / 5,5 kW
● Waste air mass flow rate ....................... 5,5 / 5,5 g/s
● Waste air temperature .......................... 260 / 260 °C
● Minimum delivery pressure at
nominal thermal output .............................13 / 13 Pa
............... 933 mm
1)

Combustion air supply

It must be guaranteed that there is enough combustion
air available for the stove. For the proper function of the
stove, a necessary combustion air volume current of
15,6 m³/h must be considered.

External combustion air connection

By an external operating mode, the combustion air
can be added from outside through a leak-proof line or
through a supply duct in the chimney. Thus, speak with
your district chimney sweep master.
Due to energy saving reasons, the combustion air in-
let should be able to be blocked if the stove is not being
operated. This can occur through a shut-off valve in the
combustion air line or through the air slide valves on
the stove. If a shut-off valve is used, this must be clear-
ly identified with CLOSED/OPEN.
Through the shutoff, it is avoided that heat is removed
from the set-up room through the constant circulation
of cold combustion air and cold combustion air lines
may lead to an increased formation of condensation.
Attention:
The combustion air line may not be closed during
operation!
In order to feed the combustion air to the stove exter-
nally via a pipe instead of from the room in which it is
installed, it is possible to screw a Ø 125 mm combus-
tion air pipe to the back of the stove. If the combus-
tion air pipe installed is longer than 3 m, calculations
will have to be carried out to verify an adequate sup-
ply of combustion air. At extremely low outdoor temper-
atures, condensation can occur on the combustion air
duct. For this reason it must be insulated with a suitable
insulating material. Observe the rules of the oven and
air heating construction craft.
Use the Olsberg combustion air pipes with sealing lip.
Attention:
Appliances with external combustion air connec-
tion are not suitable for concurrent operation with
ventilation systems, without a supplemental safe-
ty system.
11

Publicité

Table des Matières
loading

Table des Matières