M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4
Non-Spring Actuator Return for Dampers
Installation Guide
Parts Included
Warnings
Figure 1: M9335-HGA Actuator
M93xx-xGx-xx
M93xx-xUx-xx
LISTED 654U
LISTED 654U
TEMP REG EQUIP
TEMP REG EQUIP
CLASS 2
IP54
MAX
MIN
MAX
1
*140148000014B*
14-01480-00014 Rev. B
March 2022
+60°C
+140°F
-30°C
-22°F
95 % RH

Publicité

loading

Sommaire des Matières pour Johnson Controls M9320-HGA-4

  • Page 1 *140148000014B* M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 Non-Spring Actuator Return for Dampers 14-01480-00014 Rev. B Installation Guide March 2022 Figure 1: M9335-HGA Actuator Parts Included Warnings M93xx-xGx-xx M93xx-xUx-xx +60°C +140°F -30°C -22°F LISTED 654U LISTED 654U TEMP REG EQUIP TEMP REG EQUIP...
  • Page 2 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 Dimensions mm. Figure 2: The diagrams below illustrate the model dimensions of the M9300 Actuator. 30.5 Adjusting the angular rotation 14-01480-00014 Rev. B...
  • Page 3 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 Mounting Shaft diameter Small gripper Height Width Required wrench torque (Nm) Wiring Figure 3: M9320-HGA-4/M9335-HGA-4 DA DA DA DA • On/Off Control • Floating Control RED GRY RED GRY • Commande marche/arrêt • Commande flottante •...
  • Page 4 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 Figure 4: M9320-HGA-4/M9335-HGA-4 Master-Subordinate Master Subordinate 1 Master Subordinate 1 • Tandem operation RED GRY RED GRY RED GRY RED GRY • Fonctionnement en tandem • Tandem-Betrieb • Funzionamento in tandem • Funcionamiento en tándem •...
  • Page 5 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 Accessing the dip switch M9320-AUA-4/M9335-AUA-4 Command signal Setting User interface Reverse used DA Not used Direct used DA Not used used DA Not used M9320-HGA-4/M9335-HGA-4 Example Command Signal Feedback Signal Setting User Interface 2-10 0 to 10 VDC...
  • Page 6 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 Auto calibration (M9320-HGA-4/M9335-HGA-4) <3s ENTER/AUTOCAL The actuator positions the coupler to the maximum and minimum end stops to identify the range of travel. Setting the SPAN and OFFSET Proportional command signal to other value (M93xx-HGA-4) RED GRY <3s...
  • Page 7 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 INSTALLATION INSTRUCTIONS FOR THE TECHNICIAN / FITTER • READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS CAREFULLY BEFORE INSTALLING AND SAVE IT FOR FUTURE USE • All wiring should conform to local codes and must be carried out by authorized personnel only.
  • Page 8 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 POKYNY K INSTALACI PRO TECHNIKY A MONTÉRY • PŘED INSTALACÍ SI POZORNĚ PŘEČTĚTE TYTO POKYNY A BEZPEČNOSTNÍ VAROVÁNÍ A USCHOVEJTE JE PRO POZDĚJŠÍ POUŽITÍ • Veškerá zapojení by měla odpovídat místním předpisům a musí být prováděna pouze oprávněnými pracovníky.
  • Page 9 M9320-HGA-4, M9320-AUA-4, M9335-HGA-4, M9335-AUA-4 Technical specifications Product code M9320-HGA-4 M9320-AUA-4 Control type On/off floating Proportional On/off floating Power requirements 24 VAC ± 20%, 5.7 VA running Norminal AC 230 V at 50Hz: 0.04 24 VDC ± 10%, 2.1 W running Transformer sizing requirements ≥...
  • Page 10: Contact Information

    Branch offices: Principal cities worldwide Johnson Controls is registered trademark of Johnson Controls. ® All other marks herein are the marks of their respective owners. © Copyright 2022 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited. www.johnsoncontrols.com...

Ce manuel est également adapté pour:

M9320-aua-4M9335-hga-4M9335-aua-4