7. Rotating field testing
Identify a phase conducting wire as described in point 6. Now connect two phase conductors to the probe tips and
touch the finger contact. If the phase connected to probe tip L2 follows the phase connected to probe tip L1, the
phase sequence is right-handed.
"<L" LED lights up. The voltage indicator should give a reading of approx. 400V. If the only reading is 230 V, only
one phase conductor is connected.
8. Continuity / diode testing
Bring the probe tips into contact with the conductor, fuse or resistance that is being tested. From 0 ... 500 kΩ or
with the "+" probe tip at a the anode of a diode, the "Rx/Ω" LED lights up and you will hear an acoustic signal
sounds.
9. Voltage test with RCD trip test
The Tester 2550LED is equipped with a switchable load, which permits the testing of FI/RCD-safety switches. The
FI/RCD safety switch (max. 30 mA) is triggered.( max. 240V)
10. Battery replacement:
To replace the batteries, release the screw under the main casing and pull the battery compartment cover down-
ward to remove. Observe the correct polarity when inserting the new batteries.
Note: Batteries should not be disposed of as normal household waste. Take them to an approved collection point.
11. Technical Data
Display:
Voltage range:
Frequency range:
Test current:
Operation time:
Continuity test:
Type of protection:
Overvoltage class:
Safety complying:
Power supply:
12. Declaration of conformity
This product is in conformity with standards of low voltage and in accordance with the regulations 2006/95/EC,
2004/108/EC.
.
13. Fields of application
The tool is intended for use in applications as described in the operating instructions only.
Any other form of usage is not permitted and can lead to accidents or destruction of the device. Any misuse will
result in the expiry of all guarantee and warranty claims on the part of the operator against the manufacturer.
All manuals and user guides at all-guides.com
The "R>" LED lights up. If this is not the case, there is a left-turning field and the
13 LEDs for voltage (12, 24, 48, 120, 230, 400, 690 and 1000V), polarity (+~-),
continuity (Rx/Ω) and phase/rotating field (R/L) + PELV
6...1000V AC/DC
0...400Hz
~30mA
30s
0 ... 500 kΩ
IP65
CAT IV 1000V
IEC/EN 61243-3, DIN VDE 0682-401
2x 1,5V Typ AAA Micro
TESTER 2550LED
13