First Start-Up - Madas M16/RMO N.A. Mode D'emploi

Électrovanne a réarmement manuel normalement ouvert pour gaz
Masquer les pouces Voir aussi pour M16/RMO N.A.:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.4 - GENERIC EXAMPLE OF AN INSTALLATION
1. M16/RMO N.A. Manual reset solenoid valve
2. SM jerk ON/OFF valve
3. FM gas filter
4. OPSO series MVB/1 MAX shut off valve
5. RG/2MC pressure regulator
10
1
4.0 - MANUAL RESET
To reset the solenoid valve:
• Make sure the valve is NOT electrically powered;
• Close the flow downstream of the solenoid valve in order to balance the pressure between upstream and downstream when
opening;
• Push the reset handgrip (1) and wait a few seconds for the pressure upstream and downstream of the valve to stabilise;
• After balancing the pressures, pull the reset knob (1) until it connects.
• To close maually the solenoid valve (only M16/RMOC N.A. versions), push the closing push button (13).
• The red label under the manual reset (1), if visible, shows that the valve is closed.

5.0 - FIRST START-UP

• Before start-up make sure that all of the instructions on the rating plate, including the direction of flow, are observed;
• After having gradually pressurized the system, check the seal and operation of the solenoid valve, electrically
powering / disconnecting the connector ONLY IF connected to the coil.
IMPORTANT NOTE: Do not use the connector as a switch to close the solenoid valve.
• Make sure the solenoid valve is closed by electrically connecting it.
5.1 - RECOMMENDED PERIODIC CHECKS
• Check tightness of the flanged/threaded connections on the system;
• Check tightness and operation of the solenoid valve;
It is the responsibility of the final user or installer to define the frequency of these checks based on the severity of the service
conditions.
M16/RMO N.A. - M16/RMOC N.A. - MBA/RMO N.A.
8
9
2
6. MVSP/1 relief valve
7. Pressure gauge and relative button
8. Gas detector
9. SM remote jerk ON/OFF valve lever control
10. Expansion joint/anti-vibration mount
7
3
4
12
Madas Technical Manual - 3|3.1a - REV. 0 of 10
6
7
5
discharge
in open air
Oct 2018
th

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

M16/rmoc n.a.Mba/rmo n.a.

Table des Matières