Madas M16/RMO N.A. Mode D'emploi page 11

Électrovanne a réarmement manuel normalement ouvert pour gaz
Masquer les pouces Voir aussi pour M16/RMO N.A.:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.2 - INSTALLATION (see example in 3.4)
• Assemble the device by screwing it, with the due seals, onto the plant with pipes and/or fittings with the right threading for
the connection being attached.
• Do not use the coil (3) as a lever to help you screw it on, only use the specific tool;
• The arrow, shown on the body (12) of the device, needs to be pointing towards the application;
• The device can also be installed vertically without prejudicing the correct operation. It cannot be put in
upside down (with the reset knob (1) pointing downwards);
• During installation, avoid debris or metal residues from getting into the device;
• To guarantee mechanical tension-free assembly, we recommend using compensating joints, which also
adjust to the pipe's thermal dilation;
• If the device is to be installed in a ramp, it is the installer's responsibility to provide suitable supports or correctly sized
supports, to properly hold and secure the assembly. Never, for any reason whatsoever, leave the weight of the ramp only on
the connections (flanged or threaded) of the individual devices;
• In any case, following installation, check the tightness of the plant;
• Wiring cannot have cables connected directly to the coil. ALWAYS and ONLY use the connector identified by the
manufacturer;
• Before wiring the connector (5), unscrew and remove the central screw (4). Use the proper cable terminals (see figures
below). NOTE: Connector (5) wiring must be do ensuring a product rating of IP65;
• Wire the connector (5) with 3x0.75mm² cable for external Ø 6.2 to 8.1 mm. The cable to be used must be in double sheath,
suitable for outdoor use, with a minimum voltage of 500V and a temperature of at least 60 °C;
• Connect terminals 1 and 2 to the power supply and the earth cable to terminal ;
• Secure the connector (5) to the coil (3), tightening (recommended tightening torque 0.4 N.m ± 10%) the clamping screw (4);
• The valve needs to be connected to earth either through the pipe or through other means (ex. cable jumpers).
3.3 - INSTALLATION IN PLACES WHERE THERE IS THE RISK OF EXPLOSION (DIRECTIVE 2014/34/EU)
The solenoid valve is not suitable for use in zones here there is the risk of explosion.
Madas Technical Manual - 3|3.1a - REV. 0 of 10
11
Oct 2018