Desa GCN20T Manuel D'installation page 5

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

AIR FOR COMBUSTION AND
VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1.
Determine the volume of the space (length x width x height).
Length x Width x Height = ___________ cu. ft. (m
space)
Example: Space size 20 ft. (6.1 m) (length) x 16 ft. (4.88 m) (width) x
8 ft. (2.44 m) (ceiling height) = 2560 cu. ft. (72.6m
If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2.
Multiply the space volume by 20 to determine the maximum Btu/Hr
(kW) the space can support.
__________ (volume of space) x 20 = [Maximum Btu/Hr (kW) the
space can support]
Example: 2560 cu. ft. (72.6m
[maximum Btu/Hr (kW) the space can support]
3.
Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater
Gas water heater*
Gas furnace
Vented gas heater
Gas fireplace logs
Other gas appliances* + _____________ Btu/Hr (kW)
Total
* Do not include direct-vent gas appliances. Direct-vent draws com-
bustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater
Vent-free heater
Total
4.
Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.
__________________ Btu/Hr (kW) (maximum the space can support)
__________________ Btu/Hr (kW) (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (15kW) (maximum the space can support)
60,000 Btu/Hr (17.6kW) [actual amount of Btu/Hr (kW)
used]
112157-01A
3
) (volume of
3
) (volume of space)
3
) (volume of space) x 20 = 51,200
_____________ Btu/Hr (kW)
_____________ Btu/Hr (kW)
_____________ Btu/Hr (kW)
_____________ Btu/Hr (kW)
_____________ Btu/Hr (kW)
= _____________ Btu/Hr (kW)
40,000 (11.7)
_____________ Btu/Hr (kW)
20,000 (5.9)
+ _____________ Btu/Hr (kW)
60,000 (17.6)
= _____________ Btu/Hr (kW)
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
Determining Fresh-Air Flow For Heater Location
The space in the above example is a confined space because the actual Btu/Hr
(kW) used is more than the maximum Btu/Hr (kW) the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air From
Inside Building, page 6.
B.
Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 6.
C.
Install a lower Btu/Hr (kW) heater, if lower Btu/Hr (kW) size makes
room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr (kW) the space
can support, the space is an unconfined space. You will need no additional
fresh air ventilation.
WARNING: If the area in which the heater may be
operated is smaller than that defined as an unconfined
space or if the building is of unusually tight construc-
tion, provide adequate combustion and ventilation air
by one of the methods described in CAN/CGA B149.1
Natural Gas Installation Code or CAN/CGA B149.2
Propane Installation Code or applicable local code.
5 5

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Gcp20tGcn6Gcp6Gcn10tGcp10t

Table des Matières