ODMFM-R
HOLDING REGISTERS
Data type
1
Device slave address
unsigned int.
2
Modbus baud rate
unsigned int.
3
Modbus parity mode
unsigned int.
4
Device type
unsigned int.
5
HW version
unsigned int.
6
FW version
unsigned int.
7—13
Minimum temperature
14
unsigned int.
range
Maximum
15
unsigned int.
temperature range
Minimum relative
16
unsigned int.
humidity range
Maximum relative
17
unsigned int.
humidity range
18
Minimum CO
range
unsigned int.
2
19
Maximum CO
range
unsigned int.
2
Minimum temperature
20
unsigned int.
alert
Maximum
21
unsigned int.
temperature alert
Minimum relative
22
unsigned int.
humidity alert
Maximum relative
23
unsigned int.
humidity alert
24
Minimum CO
alert
unsigned int.
2
25
Maximum CO
alert
unsigned int.
2
26—29
Modbus network
30
resistor termination
unsigned int.
(NBT )
31—33
34
Active light level
unsigned int.
35
Standby light level
unsigned int.
Modbus registers
36
unsigned int.
reset
CO
module self
2
37
calibration (ABC logic)
unsigned int.
algorithm
38—40
Pour en savoir plus à propos de Modbus sur liaison série, s'il vous plaît visitez:
MIW-ODMFM-R-FR-000 - 16 / 04 / 18
TRANSMETTEUR
MULTIFONCTIONNEL AMBIANTE
Description
Modbus device address
Modbus communication baud rate
Parity check mode
Device type (Read only)
Hardware version of the device (Read
only)
Firmware version of the device (Read only) XXXX
Reserved, return "0".
Minimum value of the temperature
range; cannot be set higher than max.
temperature range minus 5ºC
Maximum value of temperature
range; cannot be set lower than min.
temperature rang e plus 5ºC
Minimum value of the rH range; cannot be
set higher than max. rH range minus 5 %
Maximum value of rH range; cannot be set
lower than min. rH range plus 5%
Minimum value of the CO
range; cannot be
2
set higher than max. CO
range minus 100
2
ppm
Maximum value of CO
range; cannot be set
2
lower than min. CO
range plus 100 ppm
2
Minimum temperature alarm value
Maximum temperature alarm value
Minimum relative humidity alarm value
Maximum relative humidity alarm value
Minimum CO
alarm value
2
Maximum CO
alarm value
2
Reserved, return "0".
Sets device as ending the line or not by
connecting NBT
Reserved, return "0".
The ambient light level above which
'Active' is indicated in input register 6
The ambient light level below which
'Standby' is indicated in input register 6
Resets Modbus Holding registers to
default values. When finished this register
is automatically reset to '0'
Enables or disables the CO
module self-
2
calibration algorithm. If enabled, the sensor
will typically reach its operational accuracy
after 24 hours of continuous operation. The
sensor will maintain its accuracy given that it
is exposed to a reference level of 400 ppm CO
at least once in a 7 day period
Reserved, return "0"
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
Retour à la Table des matières
Data
Default
1—247
0—6
0—2
ODMFM-R = 1101
XXXX
-300 — (Max. range — 50)
(Min. range + 50) – 700
0 — (Max. range — 50)
(Min. range + 50) – 1000
0 – (Max. range — 100)
(Min. range + 100) – 2.000
Min. temperature range — Max.
temperature alarm
Min. temperature alarm — Max.
temperature range
Min. relative humidity range —
Max. relative humidity alarm
Min. relative humidity alarm —
Max. relative humidity range
Min. CO
range — Max. CO
alarm
2
2
Min. CO
alarm — Max. CO
range
2
2
0—1
0—32.000
0—32.000
0—1
0—1
2
Values
1
 
0 =
1 =
2 =
2
3 =
38.400
4 =
5 =
115.200
6 =  
230.400
0 =
1
1 =
2 = 
 
0x0100 =
HW version 1.00
0x0100 =
FW version 1.00
0
100 =
10,0 °C
500
500 =
50,0 °C
50
200 =
20,0 % rH
850
850=
85,0 % rH
400
1.000 =
1.000 ppm
2.000
2.000 =
2.000 ppm
-300
100 =
10,0 ºC
700
500 =
50,0 ºC
0
200 =
20,0 % rH
1000
850 =
85,0 % rH
400
400 =
400 ppm
2.000
2.000 =
2.000 ppm
0 =
NBT disconnected
0
1 =
NBT connected
100
100=
10
10 =
0 =
0
1 =
Reset Modbus registers
0 =
Disabled
1
1 =
Enabled
4.800
9.600
19.200
57.600
8N1
8E1
8O1
100 lx
10 lx
Idle
9 - 10

Publicité