Troubleshooting - vectus ALNOR Balometer Jr. Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Troubleshooting

Symptom
Meter not at zero before use.
Cannot zero meter.
Meter reading lower than
expected.
Meter not indicating.
Meter reading higher than
expected.
Possible Cause and Corrective
Action
Velometer Jr. not adjusted. Use zero
adjustment screw.
Meter pointer not in balance. Return unit to
factory for rebalance.
Hood frame not sealing properly around
diffuser or grill. Press hood evenly against
diffuser.
Hood torn. Replace, or repair tear with duct
tape or other non-porous material.
Range selector not properly set. Make sure
detent on switch is properly engaged.
Manifold is cracked. Replace manifold.
Manifold holes are plugged. Clean holes.
Meter/range selector out of calibration.
Recalibrate instrument.
LoFlow adapter not installed when using
lowest (blue) scale. Install adapter.
LoFlow adapter not close enough to
the manifold, or installed on wrong side
of manifold. (See Preparation for Use
section.)
Range selector is switched to OFF. Position
switch to correct range.
Range selector incorrectly set. Position
switch to correct range.
Connection between manifold/range
selector/meter is broken. Repair.
Meter/range selector out of calibration.
Recalibrate instrument.
LoFlow adapter mistakenly left installed.
19