Function Check - Siemens REV34 Série Instructions D'installation

Masquer les pouces Voir aussi pour REV34 Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 8
1.1.6
Control gain (adaptation of heat output):
DIP switches 8 and 9
DIP switch 8 ON and 9 ON:
Normally sized heat output, refer to factory setting. DIP DIP
switch 8 ON and 9 OFF:
Undersized heat output:
For low boiler / flow temperatures, too small radiators
(surface) and too small volumetric flow
(nominal valve size).
DIP switch 8 OFF and 9 ON:
Oversized heat output:
For high boiler / flow temperatures, oversized radiators
(surface) and oversized volumetric flow (nominal
valve size).
DIP switch 8 OFF and 9 OFF (factory setting):
Normally sized heat output.
2
Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
seconds, press simultaneously
access the expert level for making the settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
settings by pressing
.
The expert level is quit by pressing the operating mode selection button
Code list
Function block
Code
00
Basic settings
01
10
LCD settings
11
12
30
Clock settings
31
32
Note 1: If the radio clock is not active or not present, this setting has no impact.
With the radio clock active, the time signal received from Frankfurt is shifted by the value set under code 30 (time zone).
Note 2: If the radio clock is not active or not present, the time change always takes place at 02:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
Note 3: If the radio clock is not active or not present, the time change always takes place at 03:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
3

Function check

Check the display. If there is no display, check the batteries
a)
"Continuously Comfort mode"
b)
Set the temperature setpoint to its maximum (refer to operating
c)
instructions)
The controller must deliver an OPEN signal
d)
seconds and the actuating device must travel to the fully open
position. If not:
Check actuating device and wiring
The room temperature is possibly higher than the adjusted
temperature setpoint
Select operating mode "Frost protection"
e)
The controller must deliver a CLOSE signal
f)
seconds and the actuating device must travel to the fully closed
position. If not:
Check actuating device and wiring
Room temperature may be lower than 8 °C (16 °C with setpoint
limitation)
Set temperature setpoint of "Continuously Comfort mode"
g)
the required level
Select the required operating mode
h)
CE1G2208xx
and
for 3 seconds, release
Name
Language
Sensor calibration
Illumination time
Background brightness
Contrast
Time zone
Deviation from time signal received from Frankfurt
(Central European Time CET) (refer to Note 1)
Start of summer time (refer to Note 2)
End of summer time (refer to Note 3)
, read the temperature displayed
for about 150
for about 150
Save the entry by pressing the DIP switch reset button.
1.1.7 Radio clock: DIP switch 10
Can only be used with REV..DC (with integrated DCF77 receiver for
time signal from Frankfurt)!
DIP switch ON:
DIP switch OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.8 DIP switch reset
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
and
for 3 seconds, then release the buttons and, within 3
and keep
depressed for another 3 seconds. This enables you to
on display (also refer to Fig. G).
.
Factory setting
English
off
10 seconds
0
0
0 hours
March 31 (31-03)
October 31 (31-10)
4
Reset
User-defined settings:
Press simultaneously
All temperature and time settings of the slider positions are reset to
their default values (refer to section "Factory settings" in the
operating instructions). The settings made on the expert level will
remain unchanged.
The clock starts at 12:00, the date on 01-01-08
(01 – January - 2008). During the reset time, all sectors of the
display are illuminated and can thus be checked.
All user-defined settings plus those made on the expert level:
Press simultaneously the DIP switch reset button,
for 5 seconds:
After this reset, all factory settings will be reloaded. This applies to
both the slider settings and the settings made on the expert level.
Notes
The REV34.. is an electronic room temperature controller with
7-day time switch
The controller is classified as a device of software class A and
to
designed for use in environments with normal degree of
pollution
The remote control contact must be wired separately, using a
screened cable
27.03.2008
quartz
Clock runs on built-in
Time signal DCF77 from Frankfurt
).
)
and
Your setting
,
and
for 3 seconds:
. Confirm the
and
7/44