fluidra 74148 Manuel D'instructions page 29

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 66
Current detection
circuit failure
Compressor start
failure
Ambient Temperature
device failure on Driver
board
Compressor phase
failure
EEPROM data read
malfunction
The inter-chip
communication failure
on the main control
board
Remarks:
1. In heating mode, if the water out temperature is higher than the set temperature over 7℃, LED
controller displays EE04 for water over-heating protection.
For example as below:
Output water
Mode
temperature
Heating
mode
1. Voltage signal abnormal
EE22
2. Driver board is damaged
3. Main board failure
1. Main board is damaged
2. Compressor wiring error or poor
contact or unconnected
EE23
3. Liquid accumulation inside
4. Wrong phase connection for
compressor
EE24
Ambient Temperature device failure
Compressors U, V, W are just connected to
EE25
one phase or two phases.
1. Wrong EEPROM data in the program or
EE27
failed input of EEPROM data
2. Main board failure
EE28
Main board failure
EE04 Water Overheating Protection
Set point
temperature
36℃
29℃
1. Change a new main board
2. Change a new driver board
1. Check the main board or change a
new one
2. Check the compressor wiring
according to the circuit diagram
3. Check the compressor or change a
new one
Change driver board or main board
Check the actual wiring according to the
circuit diagram
1. Re-enter correct EEPROM data
2. Change a new main board
1. Stop electricity supply and restart it
2. Change a new main board
Condition
EE04 Overheating protection
Tout -Tset
for water temperature (d2-
≧7℃
25
Malfunction
TH5)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

741497415074151Vsp-10Vsp-12Vsp-15 ... Afficher tout

Table des Matières