3.3 Distance from your swimming pool
The heat pump is normally installed within a perimeter area extending 7.5 m from the swimming pool. The
greater the distance from the pool, the greater the heat loss in the pipes. As the pipes are mostly
underground, the heat loss is low for distances up to 30 m (15 m from and to the pump; 30 m in total) unless
the ground is wet or the groundwater level is high. A rough estimate of the heat loss per 30 m is 0.6 kWh
(2,000 BTU) for every 5 ºC difference between the water temperature in the pool and the temperature of the
soil surrounding the pipe. This increases the operating time by 3% to 5%.
3.4 Check-valve installation
Note: If automatic dosing equipment for chlorine and acidity (pH) is used, it is essential to protect the heat
pump against excessively high chemical concentrations which may corrode the heat exchanger. For this
reason, equipment of this sort must always be fitted in the piping on the downstream side of the heat pump,
and it is recommended to install a check-valve to prevent reverse flow in the absence of water circulation.
Damage to the heat pump caused by failure to observe this instruction is not covered by the warranty.
3.5 Typical arrangement
Note: This arrangement is only an illustrative example.