Troubleshooting Tips; F.1 Heater Is Not Operating; F.2 Contactor Is Chattering; F.3 Contactor Is Burned Or Welded - Caloritech GE Serie Instructions D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

F.

TROUBLESHOOTING TIPS

F.1
Heater is not operating.
1.
Check all fuses.
2.
Check disconnect switch.
3.
Check voltage supplied to the heater – refer to the heater
data plate for voltage requirements.
4.
Check control voltage if transformer is installed.
5.
Check thermostat by turning it and check continuity.
6.
Check the condition of the disconnect switch if the heater is
so equipped. Measure continuity through the disconnect by
engaging the switch.
7.
Verify that there is a jumper wire present between the
terminals as per the wiring schematics (refer to Figures
3A – 3F, page 5 – 7.
8.
If problem still exists, contact factory.
F.2
Contactor is chattering.
1.
Check supply voltage.
2.
Check control voltage if transformer is installed.
3.
Check wiring connections. Tighten all loose electrical
connections.
4.
Check thermostat for continuity. If thermostat does not
break continuity replace thermostat.
5.
Check for excessive heater vibration.
6.
Do not operate if problem persists. Contact factory.
F.3
Contactor is burned or welded
1.
Check the contactor for burn marks and blackening. If
present, replace the contactor.
2.
Check incoming power to the heater to ensure there are no
voltage fluctuations.
3.
Check heating element for continuity.
4.
Check motor for continuity.
5.
Check thermostat for continuity. If thermostat does not
break continuity replace thermostat.
6.
Do not operate if problem persists. Contact factory.
F.4
Heater cycles on high limit.
1.
Check the inlet and discharge louvers for air blockage.
2.
Check for heating element fouling.
3.
Ensure motor is functioning.
4.
Do not operate if problem persists. Contact factory.
F.5
Heater is operating but no heat is present.
1.
If equipped with a "FAN ONLY" switch, ensure the switch is
in the "ON" position.
2.
Check the control voltage to the contactor coil, if unit is
equipped with a contactor and transformer. If voltage is not
within specification replace the transformer.
3.
Verify the contactor coil resistance as per Table 4,
page 11. If resistance is not within specification replace
contactor.
4.
Measure and record all element resistances. Contact
factory to verify if elements are within specifications. If not
within specification replace heating element(s).
5.
If problem persists, contact factory.
Table 4 – Resistance Values for Electrical Components
Item
Description
C11055-01
Contactor
240 V Primary
TSK4114-
Transformer
220 V
32
Secondary
480 V Primary
B11033-02
Transformer
220 V
Secondary
600 V Primary
B11033-03
Transformer
220 V
Secondary
480V Primary
Transfab
B11033-04
240 V
Transformer
Secondary
600 V Primary
Marcus
B11033-05
240V
Transformer
Secondary
600 V Primary
Transfabs
B11033-05
240 V
Transformer
Secondary
B11041-02
GE Motor 208 V to 240 V
B11059-03
GE Motor 480 V
B11059-04
GE Motor 600V
B11035-03
Thermal Cut-Out
Note:
For element resistances, please contact factory.
F.6
Heater fan does not operate but the heating elements
operate.
1.
Check motor resistance, as per Table 4, page 11 and
ensure fan blade spins freely to check motor bearings.
Replace motor as required.
2.
Do not operate unit. Contact factory.
Ω
Low
Nominal
High
0.55
0.58
0.60
5.86
6.17
6.48
6.56
6.90
7.25
23.73
24.98
26.23
6.62
6.97
7.32
36.96
38.91
40.86
6.69
7.04
7.39
135.21
142.33
149.45
43.67
45.97
48.27
218.28
229.77
241.26
43.28
45.56
47.84
215.14
226.46
237.79
39.36
41.43
43.50
45.45
47.84
50.23
45.45
47.84
50.23
57.32
60.34
63.36
-
0.10
-
11

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Ge203ctl-d

Table des Matières