Parameter Meaning
Switch-on delay after power-on
for staggered switch-on of several equipment units.
Minimum ON time
Minimum OFF time
Here you can set the time for which the equipment unit, for instance, has to
remain switched on or off. These values depend on the heating or cooling
unit being used (observe manufacturer's specifications).
In the event of a probe error, the relay is operated immediately as set in
parameter S.Er.
Alarms
Low alarm limit
As soon as the process value falls below this limit, the alarm message
is displayed, see Chapter 7 "Alarm messages".
High alarm limit
As soon as the process value goes above this limit, the alarm message
is displayed, see Chapter 7 "Alarm messages".
Alarm hysteresis
The hysteresis that was set is below
Alarm suppression time
An alarm from
present for longer than
or above
or
is not displayed for this time. If an alarm is
, then it will be displayed.
Value range
from...factory-set...to
0 ... 60min
0 ... 999 s
0 ... 999 s
-999 ... -200 ... +999
-999 ... 500 ... +999
0.2 ... 1.0 ... 99.9
.
0 ... 60 min