Re-assemble the front panel, breech plate, limit control and
burner in opposite sequence to their removal.
9.
Follow the instructions for starting the burner for the first time to
cure the firepot and perform combustion checks.
1.3)
Drawer assembly:
Remove the drawer assembly. Clean all foreign matter from the
retention head and electrodes. If a Beckett AFG burner has been
installed, the burner will have to be removed to check the retention
head and to check for proper "Z" dimension with the Beckett "T" gauge
supplied with every burner. Check for any sign of oil boiling out of the
nozzle and caulking - the solenoid valve could be leaking (if
applicable).
1.4)
Nozzle:
Replace the nozzle with the one specified in table #4.1 to #4.3.
1.5)
Oil filter:
Tank filter:
The tank filter should be replaced as required.
Secondary filter:
The 10 micron (or less) filter cartridges should be replaced annually.
Model :
Date of installation of the furnace :
Service telephones - day :
Dealer's name and address :
RESULT OF START-UP TEST
Nozzle:
Burner adjustments :
2
CO
:
%
Gross stack temperature:
Ambiant temperature:
Chimney draft:
Overfire draft :
Test made by :
20
INFORMATION
Primary air
Fine air
Draw Assembly
Smoke scale :
1.6)
Air filters:
Air filters are the disposable types. The disposable filters should be
replaced on at least an annual basis. Dusty conditions, presence of
animal hair etc. may demand much more frequent filter changes. Dirty
filters will impact furnace efficiency and increase oil consumption.
1.7)
Motor lubrication:
Do not lubricate the oil burner motor or the direct drive blower motor
as they are permanently lubricated.
1.8)
CAS -2B
venting):
If used, check the CAS-2B combustion air kit for proper operation.
Check to see that the inlet screen is not plugged. Block the air inlet
completely and ensure that a zero smoke reading results. If a zero
smoke reading is not obtained, set up the burner as indicated in table
# 4.1, # 4.2 or # 4.3.
Gradually block off the intake. The CO2 should increase by a
maximum of 0.5 percentage points at the fully blocked condition. If
not, check that the VRV gate is pivoting freely and that the pivot rod is
in a horizontal position. Also, check that the counterweight has been
properly adjusted in accordance with the CAS-2B installation
instructions.
PART 4
Serial number:
Night :
Pressure :
combustion
air
kit
(Bacharach)
(chimney
lbpsi
0
F
0
F
" C.E.
" C.E.