Télécharger Imprimer la page

afriso Eurovac HV Manuel D'utilisation page 71

Masquer les pouces Voir aussi pour Eurovac HV:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

4.4
Function
Via the suction line, the vacuum pump installed in the product generates a
vacuum in the interstitial space of the tank (vacuum range). The pressure
switch measures the vacuum in the interstitial space via the measuring line
and keeps it at a constant level together with the vacuum pump.
If a leak occurs in the tank's wall or in the leak protection lining (in the inner
or outer wall of the tank) either above or below the level of the stored liquid
or the ground water, and if this leak is greater than the suction capacity of the
vacuum pump, the vacuum will drop. When the alarm threshold for the
switching point is reached, the red alarm lamp and the audible alarm are acti-
vated and the relay is energised. The audible alarm can be switched off by
pressing the Off key.
4.5
Operating modes
The product is equipped with an output relay to transmit the alarm signal to
additional external equipment. If no error condition is present, the relay is de-
energised; in case of an alarm, the relay is energised.
The product can be operated with or without additional external equipment.
The following external equipment can be used:
• Visual and audible alarms
Remote alarm equipment
Building control systems
4.5.1
Products with EnOcean® wireless module
In the case of an alarm, the wireless module transmits the alarm message
via EnOcean® wireless technology in addition to the visual and audible
signals.
4.6
Approvals, conformities, certifications
The product complies with:
EMC Directive (2014/30/EU)
Low Voltage Directive (2014/35/EU)
Construction Products Directive 305/2011 (EN 13160-2:2003)
RoHS Directive (2011/65/EU)
The product with EnOcean® wireless also complies with:
Radio and Telecommunications Terminal Equipment Directive
(1999/5/EC)
Product description
Eurovac HV
EN
14

Publicité

loading