Terminal 3
= Relay (arm)
Terminal 4 = Relay
(N/C contact)
Terminal 5 = Relay (N/O contact)
n
Terminal
6 is internally connected to terminal 2.
6 pole DIP switch
Various wind and rain parameters and operating modes can be set by
means of the integrated 6 pole DIP switch.
Once the sensor is installed and operational, the DIP switches
should be set to the settings as shown below:
Connection (DIP switch 6 = off)
1
2
3
Switch 1
OFF
Switch 2
OFF
AC/DC
AC/DC
Switch 3
ON
Switch 4
ON
Supply
Switching
Switch 5
OFF
voltage
"Closes when wind and/or rain"
contact (N/O)
Switch 6
OFF
Central unit
IMPORTANT: Factory setting = Test setting.
Note: In the test setting, activation and drop out delay is deactivated!
Connection (DIP switch 6 = on)
If the red light-emitting diode in the sensor is lit, the sensor has been
automatic trip in the event of a supply voltage failure
activated by wind and/or rain and the modular skylight closes.
1
2
3
Other settings are possible. It is, however, not advisable to use the
10 m/s, 12 m/s or 14 m/s wind speed settings as there is the risk of dam-
AC/DC
AC/DC
age to fittings before the skylight can close fully. These settings are used
at your own discretion.
Supply
Switching
voltage
DIP switch settings for wind speed
"Opens when wind, rain and/or supply voltage failure"
contact (N/C)
Central unit
Approx
Test
3 m/s
Switch 1
OFF
ON
Switch 2
OFF
OFF
Switch 3
OFF
OFF
DIP switch setting for wind activation delay
2 seconds
Switch 4
OFF
DIP switch setting for wind/rain drop out delay
10 minutes
Switch 5
OFF
DIP switch setting for monitoring (not supported by the system)
Switch 6
Connection to power supply unit 3UC A02 and interface KLF 100
Terminal 1: Supply voltage AC/DC
Terminal 2: Supply voltage AC/DC
Terminal 3: Relay (C)
Terminal 4: Relay (N/C contact)
Terminal 5: Relay (N/O contact)
Note: Please refer to the instructions for these products that are for
indoor installation only.
6 VELUX
®
4
5
6
4
5
6
Approx
Approx
Approx
Approx
Approx
4 m/s
6 m/s
8 m/s
10 m/s
12 m/s
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
5 seconds
ON
20 minutes
ON
OFF
ON
Approx
14 m/s
OFF
ON
ON
ON
ON
ON
3UC AO2 230 volt
EU
6
OFF
5
1
2
4
3
4
3
5
6
2
1
C
KLF 100
UK
EU
ON
230 volt
UK
VELUX
7
®

Publicité

loading