GEZE TS 5000 R-ISM BG Mode D'emploi page 22

Table des Matières
Les langues disponibles

Les langues disponibles

Initial operation
7.3
Adjusting electrical hold-open device
Moving leaf is shown.
Open door leaf to desired hold-open angle and fix it there (1.).
X
Remove cable protection foils from guide (2.).
X
Loosen clamping screws of electrical hold-open device (3.).
X
Move electrical hold-open device until catch contacts sliding block (4.).
X
Screw down electrical hold-open device securely (5.).
X
To prevent loops from forming, tighten cable and fasten cable protection at hold open device end (6.).
X
Stow away (7.) loose cable in the cable protection and free area.
X
Secure exposed cable with the cable protection film (8.).
X
CAUTION!
Check free upward movement of the rocker!
X
9.
If necessary, the holding force can be adjusted (9.). According to EN 1155, the release torque should
amount to 40 Nm - 120 Nm for a door with 90° hold- open angle.
7.4
Mounting cover panel
CAUTION!
Do not pinch cable.
X
Clip on middle cover panel and moving-leaf cover panel (1.).
X
Check whether the smoke detector opening is located directly over the smoke detector.
Insert inspection caps between cover panels (2.).
X
GB 11
TS 5000 R-ISM BG
Fig.: 7.3.1
Fig.: 7.4.1
Table des Matières
loading

Table des Matières