en
2 Description of the product
2
Description of the product
2.1
Introduction to the controls platform
Fig.1
Generic example
SCB
MK
Tab.1
Components in the example
Item
Description
CU
Control Unit: Control unit
CB
Connection Board: Connection PCB
SCB
Smart Control Board: Expansion PCB (option
al)
MK
Control panel: Control panel and display
RU
Room Unit: Room unit (e.g. a thermostat)
L-Bus
Local Bus: Connection between devices
S-Bus
System Bus: Connection between appliances
R-Bus
Room unit Bus: Connection to a room unit
A
Device
B
Appliance
C
System
Tab.2
Devices covered in this manual
Name visi
Software
ble in dis
version dis
play
played on
SCB-10
01.03
2.2
Connection options for the expansion PCB - SCB-10
4
This device is compatible with the controls platform. This is a modular
system, and offers compatibility and connectivity between all products that
make use of the same platform.
R-Bus
CU
CB
L-Bus
S-Bus
Software
Description
version dis
played on
1.03
Expansion PCB SCB-10
Different heating zones can be connected to the SCB-10 PCB.
RU
Function
The control unit handles all basic functionality of the appli
ance.
The connection PCB is used to provide easy access to all
connectors of the control unit.
An expansion PCB can be fitted to an appliance to provide ex
tra functionality, like an internal calorifier or multiple zones.
The control panel is the user interface to the appliance.
A room unit is used to measure the temperature in a reference
room.
The local bus provides communication between devices.
The system bus provides communication between appliances.
The room unit bus provides communication to a room unit.
A device is a PCB, display or a room unit.
An appliance is a set of devices connected via the same L-
Bus
A system is a set of appliances connected via the same S-Bus
Function
The SCB-10 provides functionality for one DHW and
three central heating zones, a 0-10 V connection for a
PWM system pump and a potential-free contact for sta
tus notification.
control of 2 (mixing) zones fitted on connector X15
control of a third (mixing) zone via an PCB (= accessory) fitted on
connector X8
C
B
A
AD-3001366-01