Fig.24
Telephone connector
Status
0-10V
-
+
4
3
2
1
Fig.25
R-bus connectors
C
B
A
R-Bus R-Bus R-Bus
Fig.26
System sensor connectors
1
2
Tsyst Tsyst
Fig.27
DHW sensor
Tdhw
Fig.28
Contact temperature sensor
connectors
C
B
A
Tflow
Tflow
Tflow
Fig.29
Anode connector
TA
+ TA -
7747028 - v.01 - 25112019
Connect the telephone connector as follows:
1 + 2 0–10 V / status input
3 + 4 status output
AD-4000004-02
4.1.6
Connecting room thermostats per zone
The SCB-10 is fitted with three R-Bus connectors. They can be used to
connect room thermostats per zone. The R-bus connectors are related to
the other zone-specific connectors on the SCB-10.The R-Bus connector
supports the following types:
R-Bus thermostat
OpenTherm thermostat
OpenTherm Smart Power thermostat
AD-4000003-01
On/off thermostat
The software recognizes which type of thermostat is connected.
4.1.7
Connecting system sensors
Connecting system sensors (NTC 10k Ohm/25°C) for circuits (zones).
AD-4000008-02
4.1.8
Connecting the domestic hot water (DHW) sensor
Connecting the domestic hot water (DHW) sensor (NTC 10k Ohm/25°C).
AD-4000009-02
4.1.9
Connecting contact temperature sensors
Connecting contact temperature sensors (NTC 10k Ohm/25°C) for system
flow, DHW temperatures or zones (groups).
AD-4000007-02
4.1.10
Connecting the calorifier tank anode
Connecting a TAS anode (Titan Active System) for a calorifier tank.
Connect the anode as follows:
+ Connection on the calorifier tank
- Connection on the anode
Caution
If the calorifier tank does not have a TAS anode, connect the
simulation anode (= accessory)
AD-4000005-02
en
4 Installation