Assistant De Configuration Pour Les Applications En Boucle Fermée - Danfoss VLT HVAC Basic Drive FC 101 Guide Rapide

Masquer les pouces Voir aussi pour VLT HVAC Basic Drive FC 101:
Table des Matières

Publicité

Programmation
Assistant de configuration pour les applications en boucle fermée
PM motor
1-24 Motor Current
3.8
A
1-25 Motor Nominal Speed
3000
RPM
1-26 Motor Cont. Rated Torque
5.4
Nm
1-30 Stator Resistance
0.65
Ohms
1-39 Motor Poles
8
1-40 Back EMF at 1000 RPM
57
V
6-22 T54 Low Current
04.66
A
6-24 T54 low Feedback
Hz
0016
6-23 T54 high Current
13.30
A
6-25 T54 high Feedback
0050
Hz
Illustration 4.5 Assistant de configuration pour les applications en boucle fermée
MG18A904
Guide rapide
0-03 Regional Settings
[0]
Power kW/50 Hz
0-06 Grid Type
[0]
200-240V/50Hz/Delta
1-00 Configuration Mode
[3]
Closed Loop
1-10 Motor Type
[0]
Asynchronous
Motor type = IPM
1-38 q-axis inductance(Lq)
5
mH
Motor type = SPM
(1-70) PM Start Mode
[0]
Rotor Detection
1-46 Position Detection Gain
100
%
30-22 Locked Rotor Detection
[0]
Off
30-23 Locked Rotor Detection Time[s]
0.10
s
4-19 Max Ouput Frequency
0065
Hz
1-42 Motor Cable Length
50
m
4-12 Motor speed low limit
0016
Hz
4-13 Motor speed high limit
0050
Hz
3-41 Ramp 1 ramp-up time
0010
s
3-42 Ramp1 ramp-down time
0010
s
Motor type = PM motor
20-00 Feedback 1 source
[1]
Analog input 54
3-16 Reference Source 2
[0]
No Operation
3-02 Min Reference
0.00
3-03 Max Reference
50.00
3-10 Preset reference [0]
0.00
%
6-29 Terminal 54 Mode
Current
[1]
Voltage
6-26 T54 Filter time const.
0.01
s
20-81 PI Normal/Inverse Control
[0]
Normal
20-83 PI Normal/Inverse Control
Hz
0050
20-93 PI Proportional Gain
00.50
20-94 PI integral time
0020.00
s
1-29 Automatic Motor Adaption
[0]
Off
Danfoss A/S © 05/2017 Tous droits réservés.
Asynchronous motor
1-20 Motor Power
1.10
kW
1-22 Motor Voltage
400
V
1-23 Motor Frequency
50
Hz
1-24 Motor Current
04.66
A
1-25 Motor nominal speed
1420
RPM
1-44 d-axis Inductance Sat. (LdSat)
5
mH
(1-45) q-axis Inductance Sat. (LqSat)
5
mH
(1-48) Current at Min Inductance for d-axis
100
%
1-49 Current at Min Inductance for q-axis
100
%
Motor type = Asynchronous
1-73 Flying Start
[0]
No
This dialog is forced to be set to
[1] Analog input 54
Voltage
6-20 T54 low Voltage
0050
V
6-24 T54 low Feedback
Hz
0016
6-21 T54 high Voltage
V
0220
6-25 T54 high Feedback
0050
Hz
4
4
33

Publicité

Table des Matières
loading

Table des Matières