ELECTRICAL INSTALLATION
Wiring Guidelines
NOTE: Recommended for use on inverter duty rated motors. Follow motor manufacturer recommenda-
tions for cable lengths when using variable frequency drives.

Conduit Locations and Sizing

Use appropriate strain relief or conduit connectors. Close any
open conduit holes before finishing installation.
F F r r a a m m e e 2 2 : :
1. Incoming power supply—Knockout = 1.13 in (28.7 mm),
Knockout = 1.38 in (35.0 mm).
2. Power output to motor—Hole = 1.73 in (44.0 mm), Knock-
out = 1.98 in (50.4 mm).
3. Control wiring (transducer/sensor) input—Hole and two
Knockouts = 0.5 in (12.7 mm). Tighten the seal nut to 25-
30 in-lbs (2.8-3.4 Nm) and locking nut to 15-20 in-lbs (1.7-
2.2 Nm).
4. Optional cabling for auxiliary controls—two Knockouts =
0.88 in (22.2 mm).
F F r r a a m m e e 3 3 : :
1. Incoming power supply—Knockout = 1.37 in (34.9 mm),
Knockout = 1.73 in (44 mm).
2. Power output to motor—Hole = 1.98 in (50.4 mm), Knock-
out = 2.47 in (62.7 mm).
3. Control wiring (transducer/sensor) input—Hole and two Knockouts = 0.5 in (12.7 mm). Tighten the seal nut to 25-30 in-lbs
(2.8-3.4 Nm) and locking nut to 15-20 in-lbs (1.7-2.2 Nm).
4. Optional cabling for auxiliary controls—two Knockouts = 0.88 in (22.2 mm).