cecotec ENERGYSILENCE 12000 AIR CLIMA CONNECTED Manuel D'instructions page 35

Masquer les pouces Voir aussi pour ENERGYSILENCE 12000 AIR CLIMA CONNECTED:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 53
ENGLISH
responsible for their safety, and understand the hazards involved.
Supervise young children to make sure that they do not play with
the appliance. Close supervision is necessary when the appliance is
being used by or near children.
2. PARTS AND COMPONENTS
Indoor unit
Fig. 1
1.
Front panel
2. Air filter
3. LED display
4. Signal receiver
5. Terminal block cover
6. Deflectors
7.
Emergency button
8. Airflow direction louver
Remote controller
Fig. 2.
Outdoor unit
Fig. 3.
1.
Air outlet grille
2. Outdoor unit rating label
3. Terminal block cover
4. Gas valve
5. Liquid valve
Note: The above figures are only intended to be a simple diagram of the appliance and may not
correspond to the appearance of the units that have been purchased.
Display
Fig. 4.
1.
Sleep mode
2. Temperature/error code display
3. Timer
Remote control
Fig. 5.
66
ENERGYSILENCE 12000 AIR CLIMA CONNECTED
1.
On/off
2. Mode: Auto, Cool, Dehumidifier, Fan, Heat
3. Increase
4. Decrease
5. Air flow up and down
6. Air flow right and left (only some models).
7.
Option: Sleep, Eco, Auto-clean
8. Confirm
9. On/off indoor display
10. Fan speed: Mute/Low/Low-mid/Mid/Mid-high/High/Turbo/Auto
11. Timer
12. Lock function (Hold down the increase and decrease keys to activate or deactivate it)
3. BEFORE USE
Take the product out of the box.
Clean the outside and inside of the machine with a damp cloth and wipe dry.
Check for any visible damage, if any is observed, contact as soon as possible the Technical
Support Service of Cecotec for advice or reparation.
4. PRODUCT INSTALLATION
Note:
The air conditioner must be installed by professional personnel. The installation specifications
should be subject to our after-sale service regulations.
When filling the combustible refrigerant, any sudden movement or may cause serious injuries
to human bodies objects.
A leak test must be done after the installation is completed and before the device is operated.
It is a must to do the safety inspection before maintaining or repairing an air conditioner using
combustible refrigerant in order to ensure that the fire risk is reduced to minimum.
It is necessary to operate the machine under a controlled procedure in order to ensure that any
risk arising from the combustible gas or vapour during the operation is reduced to minimum.
Requirements for the total weight of filled refrigerant and the area of a room to be equipped
with an air conditioner are shown as in the following tables.
Maximum charge and required minimum floor area
m = (4 m
) x LFL, m = (26 m
) x LFL, m = (130 m
2
2
Where LFL is the lower flammable limit in kg/m
kg/m
3
.
ENGLISH
) x LFL
2
3
, R290 LFL is 0.038 kg/m
3
, R32 LFL is 0.038
ENERGYSILENCE 12000 AIR CLIMA CONNECTED
67

Publicité

Table des Matières
loading

Table des Matières