261 (PLC: 40262)
T1SetC1
262 (PLC: 40263)
T1SetC2
263 (PLC: 40264)
T4C1
T4C2
264 (PLC: 40265)
265 (PLC: 40266)
T1SetH1
T1SetH2
266 (PLC: 40267)
267 (PLC: 40268)
T4H1
268 (PLC: 40269)
T4H2
269 (PLC: 40270)
270 (P LC: 40271 )
HB:t_T4_FRESH_C
LB:t_T4_FRESH_H
T_PUMPI_DELAY
271 (PLC: 40272)
272 (PLC: 40273)
EMISSION TYPE
Parameter of the ninth temperature curves for cooling mode,
range:5~25
, default setting: 10
Parameter of the ninth temperature curves for cooling mode,
range:5~25
, default setting: 16
Parameter of the ninth temperature curves for cooling mode,
range:(-5)~46
, default setting: 35
Parameter of the ninth temperature curves for cooling mode,
range:(-5)~46
, default setting: 25
Parameter of the ninth temperature curves for cooling mode,
range:25~60
, default setting: 35
Parameter of the ninth temperature curves for cooling mode,
range:25~60
, default setting: 28
Parameter of the ninth temperature curves for cooling mode,
range:(-25)~30
, default setting: -5
Parameter of the ninth temperature curves for cooling mode,
range:(-25)~30
, default setting: 7
The type of power input limitation, 0=NON, 1~8=type 1~8, default:0
range:0.5~6 hour, setting interval:0.5 hour,
sending value=actural value*2
range:0.5~6 hour, setting interval:0.5 hour,
sending value=actural value*2
range:2~20 hour, setting interval:0.5 hour,
sending value=actural value*2:
Bit12-15: The type of zone 2 end for cooling mode
Bit8-11: The type of zone 1 end for cooling mode
Bit4-7: The type of zone 2 end for heating mode
Bit0-3: The type of zone 1 end for heating mode