Operating Cycle - Lamborghini Caloreclima EM 35-E Notice D'installation Et D'entretien

Bruleurs a air souffle pour chaudieres classiques
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

OPERATING CYCLE

Necessary input signals
Output signals
A
Begin start up
B
Flame present
B-C
Operation
C
Control stop
TMF
High/low flame thermostat
C-D
Air shutter closure + post-purge
T11 Air shutter opening time, from 0 to max.
TW Begins with the closure of the thermostatic line or the PG. The PA must be in the rest position.
This is the waiting and self-test time lasting.
T10 Begins when the motor starts up and with the prepurge phase; it lasts for 3 seconds, within which
the PA air pressure switch must give the go-ahead.
T1 Pre-purge time, which lasts for at least 30 seconds, ending when the transformer starts up.
T3 Pre-ignition phase, it ends when the gas valve opens. It lasts for 3 seconds.
T2 Safety time, within which the flame signal must reach the EC electrode. It lasts for 3 seconds.
T4 Interval between the opening of the V1 gas valve and the opening of the second stage V2.
It lasts for 8 seconds.
T6 Air shutter closing time and program zero-setting time.
T12 Time in which the air shutter shifts to the start-up position.
UK
TC-PG
Thermostats/Gas pressure
switch line
MB
Burner motor
PA
Air pressure switch
TR
Ignition transformer
V1º-V2
1
/2
stage gas valve
st
nd
EC
Control electrode
MT
Air servo control
38
M

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Em 40/2-eEm 40/m-e

Table des Matières