Electrical Wiring
Dipswitch Setting
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Definition principles of code switches:
SWO1 is used to set capabilities of master and slave indoor units as well as indoor unit; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller).
(A) Definition and description of SW01
SW01_1
SW01_2
Address of wire
SW01_3
controlled indoor unit
SW01_4
SW01_5
SW01_6
Capability of indoor unit
SW01_7
SW01_8
[1]
[2]
[3]
[4]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
∙∙∙
∙∙∙
∙∙∙
∙∙∙
1
1
1
1
[5]
[6]
[7]
[8]
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
17
Address of wire controlled indoor unit (group address)
0# (wire controlled master unit) (default)
1# (wire controlled slave unit)
2# (wire controlled slave unit)
3# (wire controlled slave unit)
4# (wire controlled slave unit)
5# (wire controlled slave unit)
15# (wire controlled slave unit)
Capability of indoor unit
0.8HP (AW-CFV09/07-N11)
1.0HP (AW-CFV09/07-N11)
1.2HP (AWSI-CFV012-N11)
1.7HP (AW-CFV018/016-N11)
2.0HP (AW-CFV018/016-N11)
2.5HP (AWSI-CFV024-N11)
3.0HP (28K)
3.2HP (AW-CFV038/030-N11)
4.0HP (AW-CFV038/030-N11)
5.0HP (
6.0HP (
∙∙∙
AW-CFV060/048-N11 )
AW-CFV060/048-N11 )