Télécharger Imprimer la page

Function Modes 8; Auto Setup; Manual Setup; Switch Off Delay (Overrun Time) - Osram DALIeco Control Installation Et Utilisation

Masquer les pouces Voir aussi pour DALIeco Control:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

DALIeco Control
5.2 Function modes
8
Switching behavior of the preconfi gured function modes: Diagrams
Single Office
Open-plan office
Corridor
PROG
Meeting room/classroom
Sanitary room
Staircase

5.3 Auto setup

Sets the target value of light regulation to 80% of maximum lighting intensity.
1.
Press the push-button [Auto setup] (SP) to start the calibra-
CH-1
CH-2
Auto
tion. After 3 minutes calibration, the lighting fl ashes and
setup
automatic light regulation starts.
Note: No settings can be made during "Auto setup". "Prog"
Manual
setup
mode is terminated automatically after "Auto setup" has been
carried out.

5.4 Manual setup

Saves the set value to any adjustable value.
CH-1
CH-2
1.
Press the push-button rocker [CH-1] top/bottom to set the
Auto
setup
target value for control.
Manual
setup
2.
Press the push-button [Manual setup] (SP), to save the cur-
CH-1
CH-2
Auto
rent lighting intensity as the set value (lamps fl ash).
setup
Manual
setup
Note:
i
As long as the setpoint storage process is running, the sensor LED will fl ash alternately
red/green. The program mode may only be terminated approx. 10 s after the process
has been completed. To avoid confusion regarding the measured value at the time of
storage, no one must be present near the sensors during the setpoint storage process.
28
9
to
14 .
9
10
11
12
13
14

5.5 Switch off delay (overrun time)

The timer is set until exiting the "ON" condition (change to "STANDBY" or "OFF") according to
the last detection of motion. In the function modes "Corridor", "Staircase" and "Sanitary", the
timer is started by switching on the lighting, even if the motion sensing is deactivated. This
permits time-dependent control also with purely manual operation.
1.
Press push-button [Switch off delay 3 min] (SP) to set an over-
test
Switch off delay
run period of 3 minutes for CH-1 and CH-2.
1 sec
30 sec
1 min
3 min
5 min
10 min
15 min
30 min
60 min

5.6 Stand-by level

Set the brightness (%) in STANDBY or switch the STANDBY function off.
Stand-by-level
1.
For example, press push-button [stand-by level 30%] (SP
OFF
10 %
30 %
50 %
or LP) to set STANDBY for CH-1 (CH-2 follows, if necessary,
with OFFSET
Stand-by-level
2.
Press push-button [stand-by level OFF] (SP or LP) to switch
OFF
10 %
30 %
50 %
STANDBY function off.

5.7 Stand-by-time

Set the duration of STANDBY or switch the STANDBY function to continuous.
Stand-by-time
Press one of the push-buttons [Stand-by-time] (SP or LP) to
30 s
5 min
ON ON
ON
ON
ON ON
set STANDBY time for CH-1 and CH-2.
If [Stand-by-time ∞] is selected, the lighting never switches off.
Semi
Semi
emi
Semi
Semi
emi
15 min
30 min
A
Auto
Auto
Auto
A
Auto
60 min
O O F F F
OFF
O O F F F
OFF
GB
5.10).

Publicité

loading