5
Connection
Sensors up to a total length of 25 m or a total area of 5 m
The contact elements are to be connected in series and the last sensor will have a quiescent
current resistance, which is 8.2 kΩ.
If sensors are only connected to one sensor input, the other sensor input must be terminated,
otherwise a "Sensor Error" fault will be displayed. The supplied 8.2 kΩ resistance can be used
for this purpose.
6
Block diagram and terminal assignment
1
Sensor 1
2
3
Sensor 2
4
5
*
6
9
10
Terminal
1
Sensor 1
2
Sensor 1
3
Sensor 2
4
Sensor 2
5
External reset
6
External reset
7
Signal relay
8
Signal relay
* Versions with automatic reset have this function integrated in the circuit.
For versions with external reset, a button must be connected to 5-6 as a normally closed contact.
7
Wiring
P
1
Sensor 1
2
3
Sensor 2
4
5
*
6
9
10
N
Connection example for single-phase drive without contactor relay
P
1
Sensor 1
2
3
Sensor 2
4
5
*
6
9
10
N
Connection example for machine controller
4
can be connected per sensor input.
2
12
13
15
16
7
8
Terminal
9
Operating voltage
10
Operating voltage
11
12
Safety output 1
13
Safety output 1
14
15
Safety output 2
16
Safety output 2
12
13
15
16
7
8
M
12
13
15
16
7
Machine
8
control
8
Maintenance and trouble shooting
After the device has been correctly mounted and installed and if the technical data are obser-
ved, it will operate without any maintenance being required. The safety system must never-
theless be checked at regular intervals for correct functioning (every month or in accordance
with higher level regulations). The sensors and feed lines must also be checked for mechani-
cal damage.
Proceed as follows if the function is not assured based on the wiring in the circuit diagram and
both yellow or red LEDs light up at the same time:
1. Press reset button (min. 1 sec.)
2. Check all sensors for actuation or damage
3. Check sensor resistances (typically 8.2 kΩ); for this measurement the sensor may not be
connected to terminals 1/2 and 3/4.
4. Start up again
There is a unit fault if both red LEDs continue to light up afterwards.
checking.
If only one yellow or red LED lights up
9

Technical data

Housing
Housing protection class
Weight
Operating voltage
according to EN 60204-1
(depending on type)
Frequency range
Power consumption
Duty cycle
Mounting
Safety output relay
Usage category
according to EN 60947-4-1**
Usage category
according to EN 60947-5-1**
Contact fuse
according to EN 60947-5-1
Contacts
Service life
Signal relay
Switching capacity**
Displays
Operation
Fault
Safety shutdown
Response time
Safety output relay
Temperature ranges
Operation
Storage
Air humidity
*For rating data not listed, please contact the factory
10
EU Declaration of Conformity
See attachment
11
WEEE
Devices with this symbol must be treated separately during disposal. This must be
done in accordance with the laws of the respective countries for environmentally
sound disposal, processing and recycling of electrical and electronic devices.
12
Contact
BBC Bircher Smart Access, BBC Bircher AG
Wiesengasse 20, CH-8222 Beringen, www.bircher.com
Designed in Switzerland / Made in Bulgaria
Return the device for
Return the device for checking.
DIN ABS, grey/black
IP20 (EN 60529)
max. 250 g (depending on type)
24 V AC/DC ±10%
115 V AC ±10%
230 V AC ±10%
50/60 Hz (45-66 Hz)
max. 5 VA
100% ED S1
35 mm mounting rail
AC-1: 230 V/2 A/460 VA, approx. 280,000 cycles
DC-1: 24 V/2 A/48 W, approx. 500,000 cycles
AC-15: 230 V/2 A/460 VA, approx. 150,000 cycles
DC-13: 24 V/2 A/48 W, approx. 80,000 cycles
2 A slow blow
positively driven relays, AgCuNi + 0.2 μm Au
mech. 10 million cycles
24 V DC / 1 A, resistive load
30 V AC / 1 A, resistive load
green
red (sensor/system fault)
yellow (sensor)
< 50 ms
-20°C to +55°C
-20°C to +80°C
max. 80% relative (no moisture condensation allowed)