Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Disconnect power before working on equipment.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
3VT General information
The 3VT circuit breakers can be delivered with rated currents I
ranging from 10 A to 630 A. For the frame size VT160 the rated
current I
varies from 32 A to 160 A.
n
Furthermore, the rated operating voltage is AC 415 / 440 V and
the rated insulation voltage is AC 690 V. The circuit breakers
are designed to be used for system and motor protection as well
as for infrequent switching of electrical circuits.
The 3VT frame size VT160 is available with thermal-magnetic
overcurrent trip units with either permanently set (fixed) or
adjustable long-time delay overload protection (L). The instanta-
neous short-circuit protection (I) is fixed.
VT160 Operating conditions
3VT circuit breakers are climate-proof. They are designed for
use in enclosed areas in which there are no severe operating
conditions (e.g. dust, corrosive vapors, damaging gases).
For installation in dusty and damp areas, suitable enclosures
(housings, cabinets) must be provided. The ambient tempera-
ture must be between+40 °C and -5 °C, and the average value
within a 24-hour period must not exceed +35 °C;
Altitude: below 2,000 m;
Pollution category: 3;
Utilization category: A.
Installation
The circuit breakers are mounted with M 5 screws in accor-
dance with the dimension drawing (1). See Figure (3) for the
permissible mounting position. The required arc blow-out space
as shown in Figure (2) must be observed.
Connection of the main and auxiliary conductors
The main terminals of the circuit breakers are equipped with box
terminals suitable for the direct connection of solid or stranded
cables. Finely-stranded conductors must be fitted with cable
end sleeves. For permissible conductor cross-sections and
tightening torques, see Table (6).
On 4-pole versions, the neutral conductor is always connected
on the left. Reverse feeding is not allowed. After connection, ter-
minal shields (optional accessories) may be fitted if required.
For information regarding the main dimensions of optional con-
nections (front extended bus bar and rear screw connection),
see Figure (4).
Operation
Toggle lever position and state indication, see Figure (9).
The circuit breaker and the switching state indicator are
operated by the toggle lever.
6
After the circuit breaker has tripped (toggle lever in "Tripped"
position), the toggle lever must be moved beyond the 0 ("OFF")
position until it relatches. Only then can the circuit breaker be
reclosed. A closed circuit breaker can be tripped (function test)
by pressing the test button.
(1)
n
(2)
Required space above arc chutes
Minimum clearance to adjacent
grounded parts as well as to non-
insulated live parts.
(4)
Extended front
terminals
Rear terminals
(screw)
English
(3)
Circuit
breaker
A5E00817850-01