Operating Malfunctions - S&P CAIB Serie Manuel D'instructions

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

O
PERATING MALFUNCTIONS
Malfunction
Cause
ü
The control panel is
ü
blank
ü
Motor is always at
low speed
(low speed)
ü
The motor never
ü
goes to
low speed
ü
(low speed)
ü
ü
Motor is always at
high speed
ü
(normal rate)
ü
ü
The motor never
goes to
ü
high speed
(normal rate)
ü
ü
ü
The heater
hardly heats or does
ü
not heat
ü
ü
ü
The heater
is too hot
ü
ü
ü
ü
Deterioration in
performances
(flow rate falls)
ü
:
Faulty controller
Controller receiving no power
Daily timer is set to low speed
(the default setting)
Actual date = holiday period
programmed to low speed
Daily timer is set to high speed
Daily timer not programmed to low
speed
Water coil frost risk detected
Daily timer is set to high speed
Actual date = holiday period
programmed to high speed
Boost function is active
Daily timer not programmed to high
speed
Actual date = holiday period
Water coil frost risk detected
Boost function not activated
Unit is badly connected
Valve incorrectly installed
Setpoint "Sp" is lower than the
temperature measured by "Sp" sensor
Error detected
(Flashing red LED on control panel)
The heater battery safety valve is badly
connected / disconnected
Valve incorrectly installed
Setpoint "Sp" is higher than the
temperature measured by "Sp" sensor
Error detected
(Flashing red LED on control panel)
The filter clogging valve is badly
connected / disconnected
Error detected
(Flashing red LED on control panel)
Solutions
ü
Check the connection and the condition of the
cable on the controller (connector not clipped on
properly, cable severed or nipped etc.)
ü
Check fuses F1, F2 and F3
ü
Check the unit's supply voltage (attention to
neutral for three-phase models)
ü
Check timers: low speed – holidays
cf: "Settings for operating periods" and "Settings for
holiday periods"
ü
Activate the "boost" function to force the motor
into high-speed for 1 h
ü
Check timers: low speed, normal speed –
holidays
cf: "Settings for operating periods" and "Settings for
holiday periods"
ü
Check the temperature reading by the sensor
against frost
if motor running at high speed:
ü
deactivate the "boost" function
Wait until timer pre-set expires (max. 1 h)
ü
Check timer settings for: normal rate – holidays
cf: "Settings for operating periods" and "Settings for
holiday periods"
ü
Deactivate the boost function. The contact should
be open when idle. Wait until timer pre-set
expires (max. 1 h)
ü
Check timers: normal rate – holidays
cf: "Settings for operating periods" and "Settings for
holiday periods"
ü
Check the temperature reading by the sensor
against frost
ü
Activate the "boost" function
check connection (contact should be closed if on
demand)
ü
Check the supply voltage (three-phase models)
ü
Check the control panel status (see above if
inactive),
ü
Check installation of the valve and its servo-motor
ü
Check values "Act" and "Sp", and position /
connection of the sensor,
ü
If an error is displayed: identify it
(press the red button on the control panel to read
the error message - consult list of errors and
troubleshooting guide)
ü
Check connection and setting of heater battery
safety valve
ü
Check installation of the valve and its servo-motor
ü
Check values "Act" and "Sp", and position /
connection of the sensor,
ü
If an error is displayed: identify it
(press the red button on the control panel to read
the error message - consult list of errors and
troubleshooting guide)
ü
Check connection and setting of filter clogging
valve
ü
If an error is displayed: identify it
(press the red button on the control panel to read
the error message - consult list of errors and
troubleshooting guide)